Allen-Bradley 1756-IB16K Installation Instructions Manual page 9

Controllogix dc digital i/o modules
Table of Contents

Advertisement

Specifications: 1756-OB16IEFS, 1756-OB16IS, 1756-OB32, 1756-OB32K, 1756-OC8, 1756-OG16, 1756-ON8
Attribute
1756-OB16IEFS
Backplane: 5.1V DC,
320 mA, 24V DC, 3 mA
Outputs: 10...30V DC, 1 A
Voltage and current ratings
max, 60 °C (140 °F),
10...30V DC, 2 A 45 °C
(113 °F) per channel
(4 channels max)
Temperature, operating
• IEC 60068-2-1(Test Ad,
Operating Cold)
• IEC 60068-2-2 (Test Bd,
0 °C< Ta < 60 °C (32 °F< Ta < 140 °F)
Operating Dry Heat)
• IEC 60068-2-14 (Test Nb,
Operating Thermal Shock)
Temperature, surrounding air, max
60 °C (140 °F)
Enclosure type rating
None (open-style)
250V (continuous),
reinforced insulation
type, outputs-
to-backplane
Isolation voltage
250V (continuous), basic
insulation type,
output-to-output
North American temp code
T4
ATEX temp code
T4
IECEx temp code
T4
Specifications: 1756-OV16E, 1756-OV32E
Attribute
1756-OV16E
Backplane: 5.1V DC, 210 mA, 24V DC, 2 mA
Voltage and current ratings
Output: 10...30V DC, SINK OUTPUT 1A Pilot Duty (DC-13/SR)
MDL OUT: 8 A max
Temperature, operating
• IEC 60068-2-1(Test Ad, Operating
Cold)
• IEC 60068-2-2 (Test Bd, Operating
0 °C< Ta < 60 °C (32 °F< Ta < 140 °F)
Dry Heat)
• IEC 60068-2-14 (Test Nb,
Operating Thermal Shock)
Temperature, surrounding air, max
60 °C (140 °F)
Enclosure type rating
None (open-style)
250V (continuous), basic insulation type, outputs-to-backplane, and output group-to-group
Isolation voltage
No isolation between individual group outputs
North American temp code
T4
ATEX temp code
T4
IECEx temp code
T4
1756-OB32,
1756-OB16IS
1756-OB32K
Backplane: 5.1V DC,
300 mA, 24V DC, 2 mA
Output: 10...31.2V DC,
Backplane: 5.1V DC,
500 mA current per
350 mA, 24V DC, 2.5 mA
channel, 50 °C (122 °F)
Output: 10...30V DC,
350 mA, 60 °C (140 °F),
2 A
1 A inrush 16 A
Pilot Duty (DC-13/SQ)
maximum current per
module 50 °C (122 °F)
10 A, 60 °C (140 °F)
250V (continuous),
reinforced insulation
type,
250V (continuous), basic
inputs-to-backplane
insulation type,
250V (continuous),
outputs-to-backplane,
basic insulation type,
and output-to-output
input group-to-group
No isolation between
individual group inputs
T4A
T3C
Rockwell Automation Publication 1756-IN062A-EN-P - August 2017
ControlLogix DC Digital I/O Modules
1756-OC8
1756-OG16
Backplane: 5.1V DC,
Backplane: 5.1V DC,
165 mA, 24V DC, 2 mA
210 mA, 24V DC, 2 mA
Output: 30 ...60V DC,
Output: 4.5-5.5V DC,
2A Pilot Duty
24 mA
(DC-13/SQ)
User Supply: 5.5V DC,
MDL: 8 A (60 °C)
384 mA, 60 °C
250V (continuous), basic insulation type, outputs-to-backplane, and output
group-to-group
No isolation between individual group outputs
T4
T4A
1756-OV32E
Backplane: 5.1V DC, 390 mA, 24V DC, 2 mA
Output: 10...30V DC, 350 mA, 60°C, 500 mA, 50°C Pilot Duty (DC-13/SS)
Group: 5 A/8 A 60°/50°C
1756-ON8
Backplane: 5.1V DC,
200 mA, 24V DC, 2 mA
Output: 10...30V AC,
50/60Hz 2A Pilot Duty
MDL: 5 A/4 A 30°/60°C
9

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents