2.0 preface The set shall not be operated with the cover removed and the cover interlocked isolator 1 The 3750 Pulpress pressurisation unit has been designed overridden. for ease of setting and operation 2 All packaged pump systems are pre-wired and fully tested, note: both hydraulically and electrically, prior to dispatch.
3750 Pulpress i n sta l l a ti o n & o p er at i ng i nstr ucti o n s pressurisation unit 6.0 typical chilled–water sealed system Air eliminator see leaflet on air eliminators electrical supply...
7 Fill the system via the quick-fill connection. Do not use the 2 Water treatment must not be added to the system via the set to fill the system. 3750 Pulpress break tank. 3 No part of the set, expansion vessel, intermediate vessel 13 .0 installation or connecting pipe is to be lagged.
& 3750 Pulpress operat in g in str uct ion s pressurisation unit 19.0 controller functions pressure par 5 - high pressure alarm = mwp(pf1) par 1 - pump cut out = fill pressure (pi) par 1 - pump cut in = (pi) - 0.2bar di erential...
3750 Pulpress i n sta l l a ti o n & o p er at i ng i nstr ucti o n s pressurisation unit 20.0 user interface normal autotest view pressure or alarm device check Press up or down for 3s = Pump test...
& 3750 Pulpress operat in g in str uct ion s pressurisation unit 22.0 par ameters 0 = no 1 = nc unit of device parameter type default min measure mode Fill pressure (Pi) Bar/25 24.9...
3750 Pulpress i n sta l l a ti o n & o p er at i ng i nstr ucti o n s pressurisation unit 23 .0 warnings and alarms Functions: • All pump(s) will stop running break tank low/high water level • Activates ‘hpr’...
Page 12
The excessive pump start alarm will be activated if the pump • Activates ‘ser’ on display starts for an excessive number of times over a certain period of time. note: Call Armstrong service to arrange service visit. alarms basic / pump delay...
Incoming water pres- Increase the water pressure, too high with Fill pressure (Pi) on data plate. To sure is not sufficient consult Armstrong Service Dept. reset consult Armstrong Service Dept. ii) Alarm 2 Pump(s) will not run symptom/cause action symptom/cause...
Page 14
t o r o n t o 23 bertrand avenue toronto, ontario canada m1l 2p3 +1 416 755 2291 b u f f a l o 93 east avenue north tonawanda, new york u.s.a. 14120 -6594 +1 716 693 8813 b i r m i n g h a m heywood wharf, mucklow hill halesowen, west midlands...