Haier MVAH018MV2AA Service Manual page 43

Constant air volume duct
Hide thumbs Also See for MVAH018MV2AA:
Table of Contents

Advertisement

[07] Communication abnormal between indoor and wired controller
If wiring of terminal A, B, C of
   wired controller is proper 
If the broken wire or port is
         fixed improperly
If in group operation
           If there is indoor unit
                 set as No. 0
If indoor unit is running
No
Yes
Yes
No
If there is indoor unit
No
      set as No. 0
If there are multi indoors
        set as No. 0
No
Yes
     If LED2 on indoor PCB is ON,
Yes
which indicate the serial signal
        sent to wired controller
     If  LED1 on indoor PCB is ON,
which indicate the serial signal
        sent to wired controller
Modify the wiring
Modify the connection
No
  Set one indoor
  unit as No. 0
Yes
No
  Set one indoor
  unit as No. 0
No
Yes
No
No
Check wired controller
PCB, if faulty, replace it
41
Set only one indoor
unit as No. 0
Check indoor PCB, if
 faulty, replace it
Yes