6. Electric characteristics

Model
Phase
MVAH018MV2AA
1
MVAH024MV2AA
1
MVAH030MV2AA
1
MVAH036MV2AA
1
MVAH042MV2AA
1
MVAH048MV2AA
1
Symbols:
MCA: Min. circuit amps (A)
MFA: Max. fuse amps of circuit breaker Output: Fan motor rated output (w) FLA: Full load amps (A)
Notes:
1. Voltage range
The units are applicable for the electrical systems where voltage supplied to unit is in the range.
2. Maximum allowable voltage unbalance between phases is 2%.
3. MCA=1.25*FLA MFA≤4*FLA.
4. Power supply uses the circuit breaker.
Units
FQY
Voltage Volt. range
50/60
220
198~242
50/60
220
198~242
50/60
220
198~242
50/60
220
198~242
50/60
220
198~242
50/60
220
198~242
Power 
Indoor fan motor
supply
MCA MFA Output (W) FLA
1.93
6.16
186
2.60
8.32
245
2.68
8.56
245
3.25  10.40
200
3.25  10.40
200
3.58  11.44
230
10
Power input (W)
Cooling
Heating
1.54
181
181
2.08
252.3
252.3
2.14
259.3
259.3
2.60
315.6
315.6
2.60
315.6
315.6
2.86
366.8
366.8