System Status Indicators

When the main thermostat screen is displayed, the on-screen labels
indicate the following.
System Operation mode indicator
"SYS OFF" displayed > System is OFF
1
"SYS MOT"
displayed > System is OFF and Minimum Off Time (MOT)
delay On is active
"HEAT ON" displayed > System is ON and heating
"COOL ON" displayed > System is ON and cooling
2
"HEAT MRT"
displayed > System is ON and heating. Minimum Run
Time (MRT) delay off is active.
"COOL MRT" displayed > System is ON and cooling. Minimum Run
Time (MRT) delay off is active.
Staging display
nd
"2
Stg" displayed > Stage 2 heating or cooling is ON
"Aux Heat" displayed > Stage 3 heating is ON
For Heat Pump systems only: "EHEAT" > emergency heat mode active
Home/Away display
Home mode is active (current setpoints are being used)
Away setback mode is active (setback setpoints are being used)
System Alerts
Alert Text displayed > Specific alert text (Filter or Maintenance Timer)
Thermostat Operation
Minimum Run Time (MRT)
The thermostat has a Minimum Run Time after the start of any heating or
cooling call. This minimum run time assures even heating and cooling
cycles. The MRT delay will keep the system on even if reaches setpoint
or you change the setpoint to a temperature that would satisfy the call,
until the MRT expires. Changing the Mode to OFF will cancel the MRT
and the system will turn off immediately. The MRT can be adjusted in the
Installer Settings menu of the thermostat.
Minimum Off Time (MOT)
The thermostat has a Minimum Off Time after any heating or cooling call
is finished. This delay prevents rapid heating/cooling cycles and also
provides "short cycle protection" for compressor calls. This delay may be
noticeable when you change a setpoint and it does not respond