Installer Settings - Capitol Energy Systems TWC46 Operation Manual

Wi-fi thermostat
Table of Contents

Advertisement

Installer Settings

When you are in the Menu Selection Screen hold down the #2 and #3
buttons to launch the Installer Settings Menu
Display Lock: Use the + and – button until you display the U button to
unlock the programming screens. The EMS sends commands to lock
these menu's when not in use to prevent changing thermostat settings.
Service Mode: Use the + and – buttons to change the test mode to Y
when servicing the HVAC unit. This will disable the EMS temperature set
point parameters for 2 hours to allow for testing the unit outside of
normal temperature set points.
System Status Indicators
System Settings:
Max Heat SP: Use the + and – buttons to adjust the maximum heat set
point. This will be set and overridden by the online EMS.
Min Cool SP: Use the + and – buttons to adjust the minimum cool set
point. This will be set and overridden by the online EMS.
Min Run Time: Use the + and – buttons to adjust the minimum run time.
The default is 3 minutes.
Min Off Time: Use the + and – buttons to adjust the minimum off time.
The default is 5 minutes.
Fan Cycler: Use the + and – buttons to adjust the minimum run time.
The default is 0 minutes for the fan ON time and 10 minutes for the fan
OFF time.
Remote Sensors
Restore Defaults: Use the arrows to select the Yes option to restore all
factory defaults.
Installer Settings
Display Lock
U
Service Mode
Network Settings
System Settings
Done
Select
Page 15