Cleaning Burners - Carrier 58MVP Service And Maintenance Instructions

Deluxe 4-way multipoise variable-capacity direct-vent condensing gas furnace for sizes 040–120, series 170
Table of Contents

Advertisement

Step 3—Cleaning Burners
The following items should be performed by a qualified service
technician. If the burners develop an accumulation of light dirt or
dust, they may be cleaned by using the following procedure:
1. Turn off gas and electrical supplies to furnace.
2. Remove main furnace door.
3. Remove burner box cover.
4. Using backup wrench, disconnect gas supply pipe from
furnace gas control valve.
Label all wires prior to disconnection when servicing con-
trols. Wiring errors can cause improper and dangerous
operation.
5. Remove wires from gas valve. Note location for reassembly.
6. Remove burner box pressure tube from gas valve regulator
fitting.
7. Remove screws that secure manifold to burner box. (See Fig.
6.)
PANEL
MANIFOLD
MOUNTING
SCREWS
Fig. 6—Burner Box Assembly
NOTE: Do not remove burner box from cell panel.
8. Remove manifold, orifices, and gas valve as 1 assembly.
9. Remove screws attaching burner assembly in burner box.
10. Remove burner assembly from burner box.
NOTE: All burners are attached to burner bracket and can be
removed as 1 assembly.
11. Clean burners with soft brush and vacuum.
12. Reinstall manifold, orifice, and gas valve assembly in burner
box. Ensure manifold seal grommet is installed properly and
burners fit over orifices.
13. Reconnect wires to gas valve. Refer to furnace wiring diagram
for proper wire location.
14. Reinstall burner box pressure tube to gas valve regulator
fitting.
CELL
MANIFOLD
GAS VALVE
REGULATOR
FITTING
GAS
CONTROL
VALVE
15. Reinstall gas supply pipe to furnace gas control valve using
backup wrench on gas valve to prevent rotation and improper
orientation.
NOTE: Use propane gas resistant pipe dope to prevent gas leaks.
DO NOT use Teflon tape.
Gas valve switch MUST be facing forward or tilted slightly.
Failure to follow this warning could result in property
damage, personal injury, or death.
16. Replace burner box cover.
17. Turn on gas and electrical supplies to furnace.
18. Check for gas leaks.
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result in
serious injury, death or property damage.
Never test for gas leaks with an open flame. Use a commer-
cially available soap solution made specifically for the
detection of leaks to check all connections. A fire or explo-
sion may result causing property damage, personal injury or
loss of life.
19. Replace main furnace door.
Step 4—Cleaning Heat Exchangers
The following items should be performed by a qualified service
technician.
PRIMARY HEAT EXCHANGERS
If the heat exchangers get an accumulation of light dirt or dust on
the inside, they may be cleaned by the following procedure:
NOTE: If the heat exchangers get a heavy accumulation of soot
GASKET
and carbon, both the primary and secondary heat exchangers
should be replaced rather than trying to clean them thoroughly due
to their intricate design. A build-up of soot and carbon indicates
that a problem exists which needs to be corrected, such as
improper adjustment of manifold pressure, insufficient or poor
quality combustion air, improper vent termination, incorrect size
or damaged manifold orifice(s), improper gas, or a restricted heat
exchanger (primary or secondary). Action must be taken to correct
the problem.
1. Turn off gas and electrical supplies to furnace.
A02312
2. Remove main furnace door.
Label all wires prior to disconnection when servicing con-
trols. Wiring errors can cause improper and hazardous opera-
tion.
3. Disconnect wires or connectors to flame rollout switch, gas
valve, igniter, and flame sensor.
4. Disconnect combustion-air intake pipe from intake housing.
5. Remove the pressure switch tube from intake housing.
6. Remove screws attaching intake housing to burner box, and
rotate intake housing away from burner box for removal.
7. Using backup wrench, disconnect gas supply pipe from
furnace gas control valve.
8. Disconnect pressure tubing from gas valve.
9. Remove 2 screws attaching top filler panel and rotate upwards
to gain access to screws attaching burner box to cell panel.
5

Advertisement

Table of Contents
loading

Table of Contents