1MRS756445
3.4.8.5.
COM600 series, Version 4.1
Modbus TCP Master (OPC) User's Manual
Binary controlled step position information (BSC)
Binary Controlled Step Position Information (BSC) for OPC server with Modbus IED
supports two subtypes:
COILED_BASE_CONTROL
DPU_REGISTER_BASE_CONTROL
Table 3.4.8.5-1 Configurable BSC properties for OPC servers with Modbus device,
subtype COILED_BASE_CONTROL
Property/Para-
Value or Value range/ Default
meter
/Example
Basic
61850-Type
BSC
Subtype
COILED_BASE_CONTROL
Addresses
Higher Coil
0 to 65535
Default: 0
Lower Coil
0 to 65535
Default: 0
Position Format
Default
Word
Integer
Long MSW first
Long MSW last
Float MSW first
Float MSW last
Bit
Default: Word
Position Register
0 to 65535
Default: 0
Stop Coil
0 to 65535
Default: 0
Description
61850-Type
Coil address for the higher command. Coil
(0X reference) address range 1 to 9999.
Address 0 equals to no information avail-
able.
Coil address for the lower command. Coil
(0X reference) address range 1 to 9999.
Address 0 equals to no information avail-
able.
Data format for the value.
Holding or input register address for the
position. Holding register (4X reference)
address range 40001 to 49999 or input
register (3X reference) address range
30001 to 39999. Address 0 equals to no
information available.
Coil address for the stop command. Coil
(0X reference) address range 1 to 9999.
0 equals to no information available.
33