ABB RET615 Product Manual page 28

Relion 615 series. transformer protection and control
Hide thumbs Also See for RET615:
Table of Contents

Advertisement

Transformer Protection and Control
RET615
Product version: 2.0
Table 26. Non-directional EF protection (EFxPTOC)
Characteristic
Operation accuracy
1)2)
Start time
Reset time
Reset ratio
Retardation time
Operate time accuracy in definite time mode
Operate time accuracy in inverse time mode
Suppression of harmonics
1) Measurement mode = default (depends on stage), current before fault = 0.0 x I
with nominal frequency injected from random phase angle, results based on statistical distribution of 1000
measurements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 x I
28
EFLPTOC
EFHPTOC
and
EFIPTOC
EFIPTOC:
I
= 2 x set Start
Fault
value
I
= 10 x set Start
Fault
value
EFHPTOC and
EFLPTOC:
I
= 2 x set Start
Fault
value
, Start value multiples in range of 1.5 to 20
n
Value
Depending on the frequency of the current
measured: f
±2Hz
n
±1.5% of the set value or ±0.002 x I
±1.5% of set value or ±0.002 x I
(at currents in the range of 0.1...10 x I
±5.0% of the set value
(at currents in the range of 10...40 x I
Minimum
Typical
16 ms
19 ms
11 ms
12 ms
22 ms
24 ms
< 40 ms
Typical 0.96
< 30 ms
±1.0% of the set value or ±20 ms
±5.0% of the theoretical value or ±20 ms
RMS: No suppression
DFT: -50dB at f = n x f
n
...
Peak-to-Peak: No suppression
, f
= 50 Hz, earth-fault current
n
n
1MRS756891 B
Issued: 01.10.2009
n
n
)
n
)
n
Maximum
23 ms
14 ms
25 ms
3)
, where n = 2, 3, 4, 5,
ABB

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents