ABB REU 523 Technical Reference Manual page 40

Combined overvoltage and undervoltage relay
Hide thumbs Also See for REU 523:
Table of Contents

Advertisement

REU 523
40
Combined Overvoltage and Undervoltage Relay
Technical Reference Manual
Settings
Table 4.1.10.4-1 Settings
Variable
Set start value of stage U>
Operate time of stage U>
Time multiplier k>
Drop-off/pick-up ratio
D/P> of stage U>
Set start value of stage U>>
Operate time of stage U>>
Time multiplier k>>
Set start value of stage U<
Operate time of stage U<
Time multiplier k<
Drop-off/pick-up ratio
D/P< of stage U<
Set start value of stage U<<
Operate time of stage U<<
Time multiplier k<<
Checksum, SGF1
Checksum, SGF2
Checksum, SGF3
Checksum, SGF4
Checksum, SGB1
Checksum, SGR1
Checksum, SGR2
Checksum, SGR3
Checksum, SGR4
Checksum, SGR5
Checksum, SGR6
Checksum, SGR7
Checksum, SGR8
Operate time of CBFP
Time setting for disabling new
trip indications on the LCD
1)
If the protection stage has been set out of operation, the number indicating the currently used value
will be displaced by "999" when parameters are read via the SPA bus and by dashes on the LCD.
Actual
Group 1
Group 2
settings (R)
(R, W, P)
(R, W, P)
S1
S41
S81
S2
S42
S82
S3
S43
S83
S4
S44
S84
1)
S45
S85
S5
S6
S46
S86
S7
S47
S87
S8
S48
S88
S9
S49
S89
S10
S50
S90
S11
S51
S91
S52
S92
1)
S12
S13
S53
S93
S14
S54
S94
S15
S55
S95
S16
S56
S96
S17
S57
S97
S18
S58
S98
S19
S59
S99
S20
S60
S100
S21
S61
S101
S22
S62
S102
S23
S63
S103
S24
S64
S104
S25
S65
S105
S26
S66
S106
S27
S67
S107
-
S121
S121
-
S122
S122
1MRS 750942-MUM
Setting range
0.60...1.40 x U
n
0.06...600 s
0.05...2.00
0.95...0.99
0.80...1.60 x U
n
0.05...600 s
0.05...2.00
0.30..1.20 x U
n
0.10...600 s
0.10...2.00
1.01...1.05
0.30..1.20 x U
n
0.10...600 s
0.10...2.00
0...31
0...255
0...255
0...63
0...255
0...15
0...15
0...15
0...15
0...15
0...15
0...15
0...15
0.10...1.00 s
0...999 min