Combined Overvoltage and Undervoltage Relay
Technical Reference Manual
Table 4.1.4.6-3 SGF2
Switch
Function
SGF2/3
Tripping of stage U<< when conventional undervoltage
measurement is in use
• 0 = normal use for detecting loss of voltage when all voltages fall
below the set value
• 1 = more sensitive tripping: the stage starts the moment one of
the phases falls below the set start value. To avoid unnecessary
start situations, the start voltage of stage U<< is to be set to 0.6 x
U
or below.
n
SGF2/4
Internal blocking of stage U< when the measured voltage falls
below 0.2 x U
• 0 = internal blocking of U<
• 1 = no internal blocking of U<
SGF2/5
Internal blocking of stage U<< when the measured voltage falls
below 0.2 x U
• 0 = internal blocking of U<<
• 1 = no internal blocking of U<<
SGF2/6
Inhibition of stage U>>
• 0 = stage U>> is not inhibited
• 1 = stage U>> is inhibited
SGF2/7
Inhibition of stage U<<
• 0 = stage U<< is not inhibited
• 1 = stage U<< is inhibited
SGF2/8
Blocking of the tripping of stage U< by the start of stage U<<
• 0 = tripping of stage U< is not blocked
• 1 = tripping of stage U< is blocked
Σ SGF2
Table 4.1.4.6-4 SGF3
Switch
Function
SGF3/1
The operation mode of the start indication of stage U>
• 0 = the start indication will automatically be cleared once the
fault has disappeared
• 1 = latching. The start indication will remain active although the
fault has disappeared.
SGF3/2
The operation mode of the trip indication of stage U>
• 0 = the trip indication will automatically be cleared once the fault
has disappeared
• 1 = latching. The trip indication will remain active although the
fault has disappeared.
SGF3/3
The operation mode of the start indication of stage U>>
• 0 = the start indication will automatically be cleared once the
fault has disappeared
• 1 = latching. The start indication will remain active although the
fault has disappeared.
SGF3/4
The operation mode of the trip indication of stage U>>
• 0 = the trip indication will automatically be cleared once the fault
has disappeared
• 1 = latching. The trip indication will remain active although the
fault has disappeared.
n
n
1MRS 750942-MUM
Default
setting
0
0
0
0
0
0
0
Default
setting
0
1
0
1