ABB REU 523 Technical Reference Manual page 38

Combined overvoltage and undervoltage relay
Hide thumbs Also See for REU 523:
Table of Contents

Advertisement

REU 523
38
Combined Overvoltage and Undervoltage Relay
Technical Reference Manual
Events to be included in the event reporting are marked with multiplier 1. The event
mask is formed by the sum of the weighting factors of all those events which are to
be included in the event reporting.
Table 4.1.10.3-1 Event masks
Event mask
Code
V155
E1...E8
V156
E9...E16
V157
E17...E24
V158
E31...E33
Table 4.1.10.3-2 Event codes E1...E8
Code
Event
E1
Start of stage U>
E2
Start of stage U> reset
E3
Trip of stage U>
E4
Trip of stage U> reset
E5
Start of stage U>>
E6
Start of stage U>> reset
E7
Trip of stage U>>
E8
Trip of stage U>> reset
Default value of event mask V155
Table 4.1.10.3-3 Event codes E9...E16
Code
Event
E9
Start of stage U<
E10
Start of stage U< reset
E11
Trip of stage U<
E12
Trip of stage U< reset
E13
Start of stage U<<
E14
Start of stage U<< reset
E15
Trip of stage U<<
E16
Trip of stage U<< reset
Default value of event mask V156
Table 4.1.10.3-4 Event codes E17...E24
Code
Event
E17
PO1 activated
E18
PO1 reset
E19
PO2 activated
E20
PO2 reset
E21
SO1 activated
E22
SO1 reset
E23
SO2 activated
E24
SO2 reset
Default value of event mask V157
Setting range
Default setting
0...255
85
0...255
85
0...255
3
0...7
1
Weighting factor
Default value
1
1
2
0
4
1
8
0
16
1
32
0
64
1
128
0
85
Weighting factor
Default value
1
1
2
0
4
1
8
0
16
1
32
0
64
1
128
0
85
Weighting factor
Default value
1
1
2
1
4
0
8
0
16
0
32
0
64
0
128
0
3
1MRS 750942-MUM