Test Run - Toshiba RAS-3M26S3AV-A Installation Manual

Multi-split type
Hide thumbs Also See for RAS-3M26S3AV-A:
Table of Contents

Advertisement

Outdoor Unit
1

0 Test run

Wiring/Piping Check
CAUTION
Electric current is applied on the
control board. Beware of electric
shock.
1. Detach the front panel of the outdoor unit.
Do not remove the air discharge grille.
2. Turn on the circuit breaker to supply electricity.
3. Start running all the indoor units connected to the outside unit in the
cooling mode.
• You need not specify the temperature setting of the indoor units.
• You cannot check wiring/piping when the external temperature is 5°C
or less.
4. Turn on the SW802 No.4 switch on the P.C board MCC 5071.
The wiring/piping check starts automatically.
While checking, each LED fl ashes consecutively to indicate that the
checking each indoor unit is in progress.
When checking is complete, the check result is displayed on the LED panel.
See the table below for details.
4-1. If no problems are detected, The checking operation returns to the
normal operation automatically.
The compressor stops temporarily, then it restarts.
The D801 LED fl ashes while the compressor is stopped.
4-2. If incorrect wiring/piping is detected, The checking operation stops.
Check the status of the LED to confi rm the details of the problem.
Turn off the circuit breaker, then check wiring/piping again.
5. Turn off the SW802 No.4 switch on the P.C board MCC 5071.
• The checking operation changes to the normal operation.
6. LED does not light if the corresponding indoor unit is not connected.
SW802
<Normal>
<Check>
LED
D800 D801 D802 D803 D804 D805
Before
check
During
check
• The D801 LED represents A unit.
• The D802 LED represents B unit.
• The D803 LED represents C unit.
• The D804 LED represents D unit.
• The D805 LED represents E unit.
1116791101_EN.indd 14
1116791101_EN.indd 14
: LED ON,
: LED OFF,
: LED Flash
Description
Normal operation (no error)
Checking A unit
Checking B unit
Checking C unit
Checking D unit
Checking E unit
LED
D800 D801 D802 D803 D804 D805
Check
results
Gas Leak Inspection
Refer to the " Gas Leak Inspection" on page 9.
Test run
1. If you perform the test run in summer, start running in the cooling mode fi rst
to decrease the temperature of the room, then run in the heating mode.
(Heating mode: Set the temperature to 30°C.)
• If you perform the test run in winter, start running in the heating mode fi rst
to increase the temperature of the room, then run in the cooling mode.
(Cooling mode: Set the temperature to 17°C.)
2. For the test run, be sure to satisfy the following conditions below:
- Perform the test run for each indoor unit respectively.
- Perform the test run for about 10 minutes in both the cooling mode and
the heating mode.
• You can perform the test run in the cooling/heating mode by utilizing the
thermo sensor of the indoor unit.
Cooling mode: Warm the thermo sensor using an appliance such as a
hair dryer.
Heating mode: Put a cold towel on the thermo sensor.
Instructions for the Customers
• Explain to the customers the proper operation procedure and let them
operate the air conditioner along with the supplied instruction manual.
• When multiple indoor units are connected to the outdoor unit, the cooling
mode and the heating mode are not available at the same time.
When multiple indoor units are running at the same time, the operation mode
of the unit which starts running fi rst is applied to the other units.
• When you start running the indoor unit or change the operation mode, the
unit starts running after 3 minutes. This is due to the protection function of
the unit, not a malfunction.
• When the external temperature becomes low, the pre-heating of the
compressor starts to protect it. Keep the circuit breaker on for use.
The electricity consumption during pre-heating is about 100 W.
If the circuit breaker is turned off, the indoor unit may not start running for
about 11 minutes.
• Electronic expansion valves are used for the outdoor unit.
When you turn on the power, the outdoor unit starts clattering every 1 or
2 months. This clattering is not a malfunction, but occurs when the unit is
returning to the default setting for optimised control.
• While an indoor unit is running in the heating mode, the outdoor unit supplies
refrigerant to the other indoor units which are not running.
Therefore, noise may come from the other indoor units or the exterior of
them may become warm.
14
Installation Manual
: LED ON,
: LED OFF,
: LED Flash
Description
Normal operation (no error)
Trouble in unit A
Trouble in unit B
Trouble in unit C
Trouble in unit D
Trouble in unit E
Trouble in units A and B
Trouble in units A and C
Trouble in units A and D
Trouble in units A and E
Trouble in units B and C
Trouble in units B and D
Trouble in units B and E
Trouble in units C and D
Trouble in units C and E
Trouble in units D and E
Trouble in units A, B, and C
Trouble in units A, B, and D
Trouble in units A, B, and E
Trouble in units A, C, and D
Trouble in units A, C, and E
Trouble in units A, D, and E
Trouble in units B, C, and D
Trouble in units B, C, and E
Trouble in units B, D, and E
Trouble in units C, D, and E
Trouble in units A, B, C, and D
Trouble in units A, B, C, and E
Trouble in units A, B, D, and E
Trouble in units A, C, D, and E
Trouble in units B, C, D, and E
"Trouble in all units
Service valve stays closed"