Figure 11: Critical Hanger Placement - Roberts Gorden CoRayVac CRT-10 Installation, Operation & Service Manual

Custom-engineered, low-intensity infrared heating systems
Hide thumbs Also See for CoRayVac CRT-10:
Table of Contents

Advertisement

CORAYVAC
®
I
NSTALLATION

Figure 11: Critical Hanger Placement

Typical Suspension Details
610 mm
min.
Part Number
Description
Turnbuckle
91903201
S-hooks
91907302
Spring Hooks
91903300
Bow Shackle
E0007576
Tube/Reflector Hanger
03090100
14 of 54
O
S
M
PERATION AND
ERVICE
ANUAL
Beam Clamp
Chain size
5 mm minimum
Rod
(10 mm)
Turnbuckle
"X"
(see
table)
Locknut
(typical)
Side View
Towards Pump
Concrete Beam
Anchor
Locknut
Screw Hook
(10 mm)
Washers
Snap Hook
2,300 mm
Run Length
15,000 mm
31,000 mm
46,000 mm
61,000 mm
76,000 mm
Wood Beam
Turnbuckle
Hanger
Reflector
Front View
Typical Expansion
Minimum "X" Length
±25 mm
300 mm
±50 mm
600 mm
±75 mm
900 mm
±100 mm
1200 mm
±125 mm
1450 mm

Hide quick links: