Clearance Data; Figure 3: Standard Reflector; Figure 4: One Side Reflector; Figure 5: Two Side Reflectors - Roberts Gorden CoRayVac CRT-10 Installation, Operation & Service Manual

Custom-engineered, low-intensity infrared heating systems
Hide thumbs Also See for CoRayVac CRT-10:
Table of Contents

Advertisement

CORAYVAC
®
I
NSTALLATION

3.2 Clearance Data

NOTE: 1. All dimensions are from the surfaces of all tubes, couplings, tees, elbows and crosses.
2. Clearances B, C and D can be reduced by 50% after 7.5 m (25') of tubing downstream
from where the burner and burner tube connect.
3. All measurements are in Millimeters.
CLEARANCES TO COMBUSTIBLES

Figure 3: STANDARD REFLECTOR

Figure 4: ONE SIDE REFLECTOR

Figure 5: TWO SIDE REFLECTORS

6 of 54
O
S
M
PERATION AND
ERVICE
A
B
D
C
A
B
D
C
A
B
D
C
ANUAL
Model
A
CRT-10
150
CRT-15
150
CRT-20
150
CRT-25
150
CRT-30
150
Model
A
CRT-10
150
CRT-15
150
CRT-20
150
CRT-25
150
CRT-30
150
Model
A
CRT-10
150
CRT-15
150
CRT-20
150
CRT-25
150
CRT-30
150
B
C
D
510
1220
510
510
1220
510
510
1220
510
920
1530
920
920
1530
920
B
C
D
305
1430
510
305
1430
510
305
1430
510
305
1530
1070
305
1530
1070
B
C
D
305
1430
305
305
1430
305
305
1430
305
305
1530
305
305
1530
305