LK Systems 11-n Assembly Instructions Manual page 11

Electric boiler
Table of Contents

Advertisement

Steady illumination
Normal operation
One long + one
Delay in connection after a power outage limits output adjustment.
short flash
One long + two
Loading relay, room thermostat or some other external control device limits output adjustment.
short flashes
One long + three
A. Overheating (maximum safe) temperature
short flashes
Connected output becomes disconnected immediately when the temperature exceeds set point value by
more than 5 °C. Reconnection takes place when temperature falls below overheating (maximum safe)
temperature.
B. Malfunction at boiler temperature sensor
Output is not switched on despite temperature being below set point value. Replace sensor. Acknow-
ledge alarm by keeping boiler switched off for 10 seconds, turn main switch to position 0.
One long + four
Remote control activated.
short flashes
Rapid flashes
By-passing of the connection delay: SNABB (Quick) button, item 13 in wiring diagram, keep button
pressed down until status indicator is illuminated steadily.
Loss of pressure
No voltage or selector in position:
UTK panel
15
12
The panel is viewable once the boiler's top support has been taken off and the automation cabinet's control
panel has been folded out.
11.
Temperature diagram: This shows the dependence of the temperature of the flow water on the selected graph and the
outside temperature.
12.
Maximum temperature: Highest allowed temperature, 60 °C, (not adjustable).
13.
Alternative temperature: The temperature of the outgoing water can be increased/decreased ±15 °C in relation to the
normal temperature. Adjustments are implemented by using the selector switch, see item 5 above.
14.
Water temperature flow rates used as the output values available on the graph are used in the floor heating calcula-
tions. If these values are not available, use graph 1 for under floor heating systems laid over a timber sub-floors. If the
loops of tubing are embedded in concrete, use a lower graph, e.g. 0.75.
15.
Minimum temperature: Lowest allowed temperature of flow water. If there is no particular requirement, do the installa-
tion for a temperature of 20 °C.
14
11
Assembly instructions | LK Electric Boiler 11-n
13
Supply settings:
Min. temp.
Graph
Alternative temp.
Max temp.
20 ºC
1
-5 ºC
60 ºC
,
EN.33.C.94.1702
11 (15)

Advertisement

Table of Contents
loading

Related Products for LK Systems 11-n

This manual is also suitable for:

623 12 24

Table of Contents