ABB REJ 527 Technical Reference Manual page 64

Directional or non-directional earth-fault relay
Hide thumbs Also See for REJ 527:
Table of Contents

Advertisement

REJ 527
64
Technical Reference Manual
Table 51: Setting group 2
Variable
Start current of stage I
>
0
Start voltage of stage U
>
0
Operate time of stage I
>/U
>
0
0
Time multiplier k of stage I
>
0
Start current of stage I
>>
0
Start voltage of stage U
>>
0
Operate time of stage I
>>/U
0
Start voltage of stage U
>
0b
Operate time of stage U
>
0b
Additional angle ϕ
of stage I
a
I
>> with basic angle
0
Basic angle ϕ
of stage I
>/I
b
0
0
Angle correction ϕ
of stage I
c
I
>> with Iϕ characteristic
0
Checksum, SGF 1
Checksum, SGF 2
Checksum, SGF 3
Checksum, SGF 4
Checksum, SGF 5
Checksum, SGB 1
Checksum, SGR 1
Checksum, SGR 2
Checksum, SGR 3
Checksum, SGR 4
Checksum, SGR 5
Checksum, SGR 6
Group 2
Setting range
(R, W, P)
S81
1.0...100 % x I
S82
2.0...80.0 % x U
S83
0.10...300 s
S84
0.05...1.00
S85
5.0...400 % x I
S86
2.0...80.0 % x U
>>
S87
0.10...300 s
0
S88
2.0...80.0 % x U
S89
0.10...300 s
>/
S90
0...90°
0
>>
S91
-90...0°
>/
S92
2...7°
0
S93
0...31
S94
0...255
S95
0...255
S96
0...32
S97
0...4
S98
0...255
S99
0...15
S100
0...15
S101
0...15
S102
0...15
S103
0...15
S104
0...15
ABB Substation Automation
Products and Systems
Customer's
Default setting
setting
1.0 % x I
n
n
2.0 % x U
n
n
0.10 s
0.05
5.0 % x I
n
n
2.0 % x U
n
n
0.10 s
2.0 % x U
n
n
0.10 s
-90°
0
0
0
0
0
0
12
3
12
3
12
3
1MRS750616-MUM

Advertisement

Table of Contents
loading

Table of Contents