ABB REJ 527 Technical Reference Manual page 26

Directional or non-directional earth-fault relay
Hide thumbs Also See for REJ 527:
Table of Contents

Advertisement

REJ 527
26
Technical Reference Manual
Table 5: SGF2
Switch
Function
SGF2/1
Automatic doubling of the start current of stage I
• 0 = The start value for the stage is not doubled at start-up.
• 1 = The start value for the stage is automatically doubled at
start-up.
SGF2/2
Inverse-time operation of stage I
stage I
>>.
0
• 0 = The inverse-time operation is not inhibited.
• 1 = The inverse-time operation is inhibited.
SGF2/3
Inhibition of the operation of stage I
• 0 = The operation of the stage is not inhibited.
• 1 = The operation of the stage is inhibited.
SGF2/4
The operation mode of the start indicator of stage I
• 0 = The start indicator automatically resets once the fault
disappears.
• 1 = The start indication remains until manually reset.
SGF2/5
The operation mode of the start indicator of stage I
• 0 = The start indicator automatically resets once the fault
disappears.
• 1 = The start indication remains until manually reset.
SGF2/6
The operation mode of the start indicator of the stage U
• 0 = The start indicator automatically resets once the fault
disappears.
• 1 = The start indication remains until manually reset.
SGF2/7
Selection of the earth-fault current or zero-sequence voltage unit.
• 0 = The unit operates with two I
deblocking facility.
• 1 = The unit comprises a three-stage zero-sequence voltage
unit.
SGF2/8
Selection of U
protection.
• 0 = U
deblocking is in use.
0
• 1 = U
deblocking is not in use.
0
Σ SGF2
> inhibited by the starting of
0
>> or U
0
-stages and a voltage
0
deblocking for the directional earth-fault
0
ABB Substation Automation
Products and Systems
Default
setting
>>.
0
0
0
>>.
0
0
> or U
>.
0
0
0
>> or U
>>.
0
0
0
>.
0
0b
0
0
0
1MRS750616-MUM