ABB REJ 527 Technical Reference Manual page 21

Directional or non-directional earth-fault relay
Hide thumbs Also See for REJ 527:
Table of Contents

Advertisement

ABB Substation Automation
Products and Systems
1MRS750616-MUM
Technical Reference Manual
RD-type characteristic
The RD-type characteristic is a special characteristic that is principally used in earth-
fault protection requiring a high degree of selectivity even at high resistance faults.
In this case, the protection can operate in a selective way even if it is not directional.
Mathematically, the time/current characteristic can be expressed as follows:
t s [ ]
×
=
5.8 1.35
log
where
t = operate time in seconds
k = time multiplier
I
= phase current
0
I
> = set start current.
0
The RD-type characteristic is illustrated in Fig. 4.1.3.5.-3.
t/s
70
60
50
40
30
20
10
9
8
7
6
5
4
3
2
1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.09
0.08
0.07
0.06
0.05
0.04
0.03
0.02
1
2
3
4
5
6
7 8 9 10
20 Io/Io>
Fig. 4.1.3.5.-1 Normal inverse and very inverse time characteristics
Io
----------------- -
×
e
k Io>
t/s
70
60
50
40
30
20
10
9
8
7
6
5
4
3
k
1.0
2
0.9
0.8
0.7
0.6
0.5
1
0.9
0.4
0.8
0.7
0.3
0.6
0.5
0.2
0.4
0.3
0.1
0.2
0.05
0.1
0.09
0.08
0.07
0.06
0.05
0.04
0.03
0.02
1
2
REJ 527
k
1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.05
20 Io/Io>
3
4
5
6 7 8 9 10
21