6.2 Electronic Expansion Valve (EXV) checking procedures
a. Check if the EXV connector is correctly connected to PCB.
b. Turn power off and on again, and check if EXV generates a latching sound.
c. If the EXV does not generate a latching sound in above step b., disconnect connector and check
continuity using a multimeter.
d. Check the continuity between pins [1-6, 3-6, 2-5, 4-5 (between pins 1-6, 2-6, 3-6, 4-6 for harness 5P
models)]. If there is no continuity between the pins, EXV coil is faulty.
e. If the continuity is confirmed in step d., outdoor PCB is faulty.
Harness 6P
6P Connector
S
2
0
1
2
3 4
6.3 Four way valve performance checking procedures
6.3.1 Class 25/35
Turn power off and then
Start heating operation.
Disconnect four way valve coil
from connector and check the
valve coil resistance at
Replace four way valve.
1 - 6
3 - 6
C
h
e
k c
2 - 5
4 - 5
5
6
(R106366)
on again.
*Four way valve coil
Heating: Energized
S80 voltage at
No
180-280V with
compressor on?
*Refer Figure 1 below.
Yes
continuity.
Four way
No
Yes
(Fig. 1)
Voltage at S80
DC180-280V
DC12-15V
Harness 5P
(5)
6P Connector
S
2
0
1
2
3 4
5
6
Not Energized
Replace outdoor PCB.
Replace four way valve coil.
Compressor
ON
Time
Refrigerant Diagram
1 - 6
3 - 6
C
h
e
k c
2 - 6
4 - 6
(R106366)
74

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents