LG BNU-LW Installation Manual page 25

Lonworks gateway
Table of Contents

Advertisement

5) Fan direction auto input/output (Only applies to air conditioner)
Function
Input
Using NV
Operation
Function
Output
Using NV
Operation
Valid Range
NV
Filed
value
SNVT_switch
state
( Index : 95 )
Default Value
6) Temperature setting input/output (Only applies to air conditioner)
Function
Input
Using NV
Operation
Function
Output
Using NV
Operation
Valid Range
NV
SNVT_switch
( Index : 95 )
Fan direction auto command input
Network input variable : SNVT_switch nviSwing_n
It controls the fan direction of each product (air conditioner/ventilation)
Fan direction auto status display
Network output variable : SNVT_switch nvoSwing_n
It monitors the fan direction of each product (air conditioner/ventilation)
not used (set in 0% usually)
0 = Fan direction fixed for air conditioner product
1 = Fan direction auto for air conditioner product
Set temperature range input
Network input variable : SNVT_switch nviSetPoint_n
It controls the temperature setting of each product (air conditioner/ventilation)
Set temperature range status display
Network output variable : SNVT_switch nvoSetPoint_n
It monitors the set temperature of each product (air conditioner/ventilation)
At Cool mode : 18 ~ 30°C
At Heat mode : 18 ~ 30°C
At Dry mode and Fan mode : Not available
Default Value
Operation
Operation
Installation Manual 25
Appendix

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pnf-b16a1

Table of Contents