FlowCon SM.1.1 Installation And Operation Instruction Manual

15-40mm, 1/2"-1 1/2" dynamic self balancing control valve

Advertisement

Quick Links

FlowCon SM 15-40mm
INSTALLATION AND OPERATION INSTRUCTION
Install the FlowCon SM valve either in the
supply or return pipe work for the unit. It is re-
commended that a strainer be installed prior to
the valve body to prevent damage or blockage
due to debris. INSTALL THE VALVE HOUSING
WITH THE FLOW DIRECTIONAL ARROW
POINTING IN THE CORRECT DIRECTION.
The valve body is available with double union
end connections. Two types of end connec-
tions are available for use with the union nut:
Threaded (male or female):
The threads on both the connection and pip-
ing should be cleaned carefully.
As these models are union end connected, the
union nuts and the end connections should be
removed for installation.
O-rings are supplied with the valve body and
are used to seal the connections. It is recom-
mended to grease the o-rings with a silicone
grease before installation. IMPORTANT: Never
use mineral oil or petrol based grease or oil
on the o-rings. Please make sure these are
in place in the o-ring grooves in the inlet and
outlet of the valve body, when installing the
housing and REMEMBER TO TIGHTEN THE
UNIONNUTS TO ENSURE SEALING.
For all threaded connections pls. clear threads
on both valve and piping of debris. Sealant such
as pipe dope or teflon tape is recommended.
WHEN USING HEMP AS PIPE SEALANT,
ENSURE NO STRANDS ARE LEFT IN THE
VALVE OR PIPING.
Soldered end (sweat):
REMOVE THE END CONNECTIONS FROM
THE HOUSING BEFORE SOLDERING. THIS
ENSURES THAT THE O-RINGS AND INTER-
NAL PARTS ARE NOT DAMAGED BY HEAT.
FlowCon SM 15-40mm, 1/2"-1 1/2"
Denmark
DYNAMIC SELF BALANCING
Valve bodies are as standard supplied with
body tappings plugged, each plug sealed with
a gasket.
Alternatively, pressure/temperature fittings
(p/t plugs) are available. Before finger mount-
ing the p/t plugs in the body tappings, pls. seal
the threads of the p/t plugs (DO NOT OVER
TIGHTEN).
Fitting and orientation
of the actuator
Pls. install the valve so that the actuator is
located upwards and not lower than the hori-
zontal line to prevent condensation into the
electronics (pls. see figure 1 below).
Max 90º
Max 90º
Dubai
USA
- 1 -
CONTROL VALVE
Max 90º
Max 90º
Singapore
www.flowcon.com
1A95100 - 08/2016
FlowCon International assumes no responsibility
for mistakes, if any, in any printed material.
Figure 1

Advertisement

loading

Summary of Contents for FlowCon SM.1.1

  • Page 1 CONTROL VALVE INSTALLATION AND OPERATION INSTRUCTION FlowCon SM 15-40mm, 1/2”-1 1/2” Install the FlowCon SM valve either in the Valve bodies are as standard supplied with body tappings plugged, each plug sealed with supply or return pipe work for the unit. It is re- commended that a strainer be installed prior to a gasket.
  • Page 2 1 and 3 (see figures 6 and 7). Socket Head Screws Spindle/Shaft Valve Body DN15/20 Figure 2 Denmark Dubai Singapore www.flowcon.com 1A95100 - 08/2016 FlowCon International assumes no responsibility - 2 - for mistakes, if any, in any printed material.
  • Page 3 4-20mA input and 2-10VDC feedback 4-20mA feedback DIGITAL TRI-STATE DIGITAL TRI-STATE Figure 6 Figure 7 2-10VDC feedback 4-20mA feedback Denmark Dubai Singapore www.flowcon.com 1A95100 - 08/2016 FlowCon International assumes no responsibility - 3 - for mistakes, if any, in any printed material.
  • Page 4 If changing to Normally Open, see below: For Normally Open set programming switch #1 to ON. Denmark Dubai Singapore www.flowcon.com 1A95100 - 08/2016 FlowCon International assumes no responsibility - 4 - for mistakes, if any, in any printed material.
  • Page 5: Manual Over-Ride Operation

    POWER. Failure to disconnect power may Press and release the cause damage to the actuator gears. Fit the reset button to memorize manual over-ride key (FlowCon No. ACC0001) this value. The indication onto the valve spindle. Press the clutch. Rotate LED should blink once as...
  • Page 6 3080 13.6 OFF OFF ON ON ON 0.301 1080 4.78 0.909 3270 14.4 OFF OFF OFF ON ON ON SM.1.1 - 0.685l/sec and 0.317 1140 5.03 0.961 3460 15.2 ON ON ON ON ON SM.2.1 - 2.34l/sec 0.332 1200 5.27 1.01...
  • Page 7 C1: P/t plug (2 pcs.) C2: Plug and gasket (2 of each) Union end connections. Figure 9 Denmark Dubai Singapore www.flowcon.com 1A95100 - 08/2016 FlowCon International assumes no responsibility - 7 - for mistakes, if any, in any printed material.
  • Page 8: Own Notes

    FlowCon SM 15-40mm DYNAMIC SELF BALANCING CONTROL VALVE Own Notes: Denmark Dubai Singapore www.flowcon.com 1A95100 - 08/2016 FlowCon International assumes no responsibility - 8 - for mistakes, if any, in any printed material.

This manual is also suitable for:

Sm.2.1