Inputs" Circuit Selection; Field Descriptions - Gamewell IdentiFlex 610 Installation & Operation Manual

Analog / addressable fire alarm
Hide thumbs Also See for IdentiFlex 610:
Table of Contents

Advertisement

"Inputs" Circuit Selection

1. From the Circuit Programming menu, Press [1] on keypad.
2. Press "Enter".

Field Descriptions

"Ckt": xx"
"Add: xxx"
"D_Type:xxx"
"Comp:x"
"Sens:x"
"R/R:x"
"FTemp:x"
"Z_Type: xxx"
"I_GRP: x"
"W1:xxx "
NOTE: The user can scroll through field variables using up/down arrow keys or enter the address number directly via the key pad.
>>NOTE: The cursor will be flashing under the circuit number. If
the device type is an ion detector Figure 8 will be displayed.
Ckt:XX Add:XXX D_Type: Ion Z_Type: XXXX
I_GRP:XXX
>>NOTE: The display starts with Circuit 1 and begins with the
highest address in circuit.
Indicates the circuit (analog line or conventional) address that has
been selected.
Shows the address of the analog device to be modified (1 - 126).
Shows the type of device (from type code of addressed device). If
the device type is a photo detector, Figure 8A will be displayed. For
a complete list of Device Types refer to Table P3.
A photo detector can be selected for operation with background
compensation (Yes) or without background compensation (no).
Default is Yes.
The sensitivity range of a photo detector can be adjusted
(compensated) to the environment. The device sensitivity range; 3
is the least sensitive and 0 is the most sensitive. The default is '2'.
If the device is a heat detector, Figure 8B will be displayed. If the
device is a heat detector, the temperature can be defined in Celsius
or Fahrenheit.
Shows the type of zone that has been selected for the device. Zone
types are defined in Zone Type Table P2.
Indicates the selected initiating group of the device. Each input
device can only be assigned to one group. One initiating group can
contain many input devices (logically arranged).
utilize up to 256 initiating groups.
Indicates the five (5) separate word dictionaries (W1 - W5) stored
and words contained in each dictionary (0 - 127 coded words for
Dict. 1 - 4, and 0 - 1024 for Dict. 5). This field is not displayed until
selected. Refer to Table P4.
Figure 8
63
The user can

Hide quick links:

Advertisement

Table of Contents
loading