Bay control REC670 2.2
Product version: 2.2.1
Table 28. Electromagnetic compatibility
Test
1 MHz burst disturbance
100 kHz slow damped oscillatory wave immunity test
Ring wave immunity test, 100 kHz
Surge withstand capability test
Electrostatic discharge
Direct application
Indirect application
Electrostatic discharge
Direct application
Indirect application
Fast transient disturbance
Surge immunity test
Power frequency immunity test
Conducted common mode immunity test
Power frequency magnetic field test
Pulse magnetic field immunity test
Damped oscillatory magnetic field test
Radiated electromagnetic field disturbance
Radiated electromagnetic field disturbance
Conducted electromagnetic field disturbance
Radiated emission
Radiated emission
Conducted emission
Table 29. Insulation
Test
Dielectric test
Impulse voltage test
Insulation resistance
56
Type test values
2.5 kV
2.5 kV
2-4 kV
2.5 kV, oscillatory
4.0 kV, fast transient
15 kV air discharge
8 kV contact discharge
8 kV contact discharge
15 kV air discharge
8 kV contact discharge
8 kV contact discharge
4 kV
(SFP galvanic RJ45: 2kV)
2-4 kV, 1.2/50 ms
high energy
150-300 V, 50 Hz
15 Hz-150 kHz
1000 A/m, 3 s
100 A/m, cont.
1000 A/m
100 A/m
20 V/m, 80-1000 MHz
1.4-2.7 GHz
20 V/m
80-1000 MHz
10 V, 0.15-80 MHz
30-5000 MHz
30-5000 MHz
0.15-30 MHz
Type test values
2.0 kV AC, 1 min.
(SFP galvanic RJ45: 1.0 kV,
1 min.)
5 kV, 1.2/50 ms, 0.5 J
> 100 MW at 500 VDC
1MRK 511 404-BEN A
Reference standards
IEC 60255-26
IEC 61000-4-18, Class III
IEC 61000-4-12, Class IV
IEEE/ANSI C37.90.1
IEC 60255-26
IEC 61000-4-2, Class IV
IEEE/ANSI C37.90.1
IEC 60255-26, Zone A
IEC 60255-26, Zone A
IEC 60255-26, Zone A
IEC 61000-4-16, Class IV
IEC 61000-4-8, Class V
IEC 61000–4–9, Class V
IEC 61000-4-10, Class V
IEC 60255-26
IEEE/ANSI C37.90.2
IEC 60255-26
IEC 60255-26
IEEE/ANSI C63.4, FCC
IEC 60255-26
Reference standard
IEC 60255-27
ANSI C37.90
IEEE 802.3-2015,
Environment A