Huawei SmartLogger2000 Quick Manual page 3

Hide thumbs Also See for SmartLogger2000:
Table of Contents

Advertisement

Port (Silk
No.
Screen)
5
SFP1, SFP2
6
ETH1, ETH2
7
DO
8
COM1–COM6
9
Default
10
AC1, AC2
11
12
AI1–AI8
13
AO1–AO6
14
DI1–DI8
2
Typical Cable Connection Scenarios
Smart Array Controller Scenario
2.1
NOTICE
1. The general input power cable for the smart array controller needs to be prepared by the
customer. Recommended cable: four-core armor cable with the operating voltage to the ground
greater than or equal to 600 V and the cross-sectional area of a single core being 4 mm
2. The cable from the busbar to the knife switch needs to be prepared by the customer.
Recommended cable: three-core armor cable with the operating voltage to the ground greater
than or equal to 600 V and the cross-sectional area of a single core being 4 mm
3. The SmartLogger and the three RS485 signal surge protective devices (SPDs) used by the
SmartLogger have been installed before delivery.
4. The SmartLogger PGND cable, AC power cable, power adapter and its power cable, and the
communications cable between the SmartLogger and the RS485 signal SPD have been
installed before delivery.
5. The PID module and inductor are configured only in the smart array controller (with a PID
module) and have been installed before delivery.
Function
Description
Ethernet optical
Connects to an ATB or another cascaded
port
SmartLogger.
Ethernet electrical
Connects to an Ethernet LAN switch, router, POE or
port
PC device.
Digital output (DO) Relay output.
Six RS485 ports that can be connected to devices
RS485
such as the inverter, box-type transformer, electricity
communications
meter, or EMI.
Resets and restarts the Bluetooth module or resets
Default key
the SmartLogger IP address to the default IP address
(valid within 5 minutes).
AC power cable
Connects to A, B, and C three-phase inputs, and used
ports
for power line communication (PLC) with the inverter.
External
N/A
grounding
Analog input (AI)
Analog output
4–20 mA, 0–20 mA current output.
(AO)
Digital input (DI)
Connects to a dry contact input.
SmartLogger2000-10: AI1–AI4: 4–20 mA and 0–20
mA input current (passive); AI5–AI8: 4–20mA and
0–20 mA input current (active)
Other models: AI1: 0–10 V input voltage (passive);
AI2–AI4: 4–20 mA and 0–20 mA input current
(passive); AI5–AI8: 4–20 mA and 0–20 mA input
current (active)
2
2
2
.

Advertisement

Table of Contents
loading