Appendix A - Acs 501 Technical Data; Input Power; Output Power; Analog Inputs - ABB ACS 501 Installation & Start-Up Manual

Adjustable frequency ac drives 1 to 75 hp, series b
Table of Contents

Advertisement

Input Power

Output Power

Analog Inputs

ACS 501 Installation & Start-up Manual
Appendix A – ACS 501 Technical Data
Voltage: 208/220/230/240 VAC ± 10% for 230 VAC units
380/400/415 VAC ± 10% for 380 VAC units
440/460/480/500 VAC ± 10% for 480 VAC units
525/550/575/600 VAC ± 10% for 600 VAC units
Frequency: 48 – 63 Hz
Displacement Power Factor: > 0.98
Line Imbalance: ± 3% of V
Voltage: 0 – V
, three-phase (full voltage at field weakening point)
N
Frequency: ACS 501, 0 – 500 Hz
ACS 502, 0 – 120 Hz
Frequency Resolution: 0.01 Hz
Continuous Current (constant torque): 1.0 x I
Continuous Current (variable torque): 1.0 x I
Maximum Current (1 min/every 10 min): 1.5 x I
Short Time Overload (2 sec/every 1 min): 2.0 x I
Overcurrent Trip: 3.75 x I
Field Weakening Point: ACS 501, 30 – 500 Hz
Field Weakening Point: ACS 502, 30 – 180 Hz
Continuous Loadability of Motor: 100% at rated speed (for F class motor)
Modulation Frequency: ACS 501, 1 – 12 kHz
Two programmable analog inputs.
Current Reference: 0 – 20 mA, R
• Minimum: 0 mA / 4 mA / 0 – 20 mA
• Maximum: 0 – 20 mA
Voltage Reference: 0 - 10 V, R
• Minimum: 0 V / 2 V / 0 – 10 V
• Maximum: 0 – 10 V
Potentiometer: 1K – 10K ohms
Potentiometer Reference Voltage: 10 V, 10 mA
R
R
RSQ
instantaneous, 2.65 x I
N
ACS 502, 3 kHz
= 250 ohms
I
= 200K ohms
I
N
N
(RMS)
N
A-1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents