CAC / BDP KSACN0201AAA Owner's Manual page 9

Wired controller for high wall ductless systems
Table of Contents

Advertisement

Figure 18 displays the wired remote controller installation steps.
NOTE: There are several issues that require the installer's attention.
1. Prior to the installation, cut off the power supply to the wire buried in the installation hole.
2. Remove the four−core twisted pair line from the installation holes and run them through the rectangular hole behind the wired remote
controller plate.
3. Secure the wired remote controller plate to the wall, over the installation hole, and then secure the plate with the screws (M4X25).
4. Insert the four−core twisted pair line into the wired remote controller slot and then buckle the front panel and the plate of the wired
remote controller together.
5. Secure the front panel and the wired remote controller plate tightly with the screws (ST2.9X6).
CAUTION
!
Please pay special attention to the following directions
during the connection to avoid air conditioning malfunction
due to electromagnetic interference.
1. Separate the wired remote controller signal and
communication lines from the power cord and connection
lines between the indoor and outdoor unit, with a
minimum interval of 7.8 in (20cm), otherwise the unit's
communication will probably malfunction.
2. If the air conditioning unit is installed in close proximity to
an electromagnetic interference, the signal and the wired
remote controller communication lines must be shielded by
twisted pair lines.
1
2
7
8
Fig. 18 - Installation Steps
3
4
6
5
9
10
DISASSEMBLY OF THE WIRED REMOTE
CONTROLLER
Figure 19 displays the disassembly of the wired remote controller.
1
2
Fig. 19 - Disassembly of the Wired Remote Controller
9
3
4

Advertisement

Table of Contents
loading

Related Products for CAC / BDP KSACN0201AAA

Table of Contents