Electrical Tables. Refrigerant: P = R410a Voltage Code: 1 = 230-1-60 VAC 2 = 208-3-60 VAC 4 = 460-3-60 VAC 5 = 575-3-60 VAC 6 = 220-1-50 VAC 7 = 380-3-50 VAC Boreal Geothermal Inc. Page 2 02 JULY 2009...
Page 3
C or Z C or Z HACW C or Z C or Z HACW C or Z C or Z HACW This manual applies only to the models and revisions listed in this table 02 JULY 2009 Page 3 Boreal Geothermal Inc.
A properly qualified electrician should be retained to UNIT DESCRIPTION make the connections to the heat pump and associated The W-Series unit is a high efficiency two-stage geother- controls. The connections to the heat pump MUST CON- mal heat pump with R410a refrigerant. Two-stage units offer a FORM TO LOCAL CODES.
The high and low pressure controls are monitored at all times, the compressor will not be able to start if either of them has a fault. 02 JULY 2009 Page 7 Boreal Geothermal Inc.
The DHW loop may have to be purged of air several times before good circulation is obtained. A temperature difference between the DHW In and DHW Out can be felt by hand when the circulator pump is operating properly. Boreal Geothermal Inc. Page 8 02 JULY 2009...
Fan coils can be used to provide heating and/or cooling for BOREAL GEOTHERMAL INC. HIGHLY RECOMMENDS areas that do not have radiant in-floor heating. They provide a THAT A PROPER HEAT LOSS/GAIN ANALYSIS BE PER- means of air heating/cooling with minimal or no ductwork. Note...
Page 13
02 JULY 2009 Page 13 Boreal Geothermal Inc.
Page 14
Boreal Geothermal Inc. Page 14 02 JULY 2009...
30 to 40 psig. on the lines when the heat pump is operating. However in some cases a well can supply a heat pump only if the minimum requirement for water is used. 02 JULY 2009 Page 15 Boreal Geothermal Inc.
Page 16
Boreal Geothermal Inc. Page 16 02 JULY 2009...
Page 17
Boreal Boreal Boreal 02 JULY 2009 Page 17 Boreal Geothermal Inc.
Optional fittings with P/T ports are CIRCULATOR PUMP MODULE available for the circulator pump modules sold by Boreal Geothermal Inc.. Boreal Geothermal Inc. has compact pump modules with built in three way valves to facilitate filling and purging the FLUSHING &...
The following steps describe how to perform the startup procedure of the geothermal heat pump. The W-Series Two-Stage R410a Startup Record located in this manual is used in conjunction with this startup procedure to pro- vide a detailed record of the installation. A completed copy should be left on site, a copy kept on file by the installer and a copy should be sent to Boreal Geothermal Inc.
3. Do a final check for leaks in the ground water / ground loop system and ensure the area is clean. 4. Leave a copy of the Startup Record at the installation site, send a copy to Boreal Geothermal Inc. and keep the final copy.
Startup Record Sheet—W-Series Size 25-75 Two-Stage R410a Installation Site Startup Date Installer City Company Province Check boxes unless Model asked to record data. Country Serial # Circle data units. PRE-START INSPECTION Indoor Loop All shut-off valve are open (full flow available)
Disconnect the purge cart and set the pump module valves back to the original positions. STEP 10 Operate the system and check for improved performance. *Depending on the plumbing, there should be either unions or boiler drains for to access the heat exchanger. Boreal Geothermal Inc. Page 24 02 JULY 2009...
Correct the wiring. heat pump and aquastats. and COM at the top of the aquastat. Faulty aquastat. 24VAC is present across 24V Replace aquastat. and COM of the aquastat but there is no display. 02 JULY 2009 Page 25 Boreal Geothermal Inc.
Page 26
Faulty control board. 24VAC is present across each Replace control board. FLOW SWITCH terminal and C, but not voltage is present across CC on the control board and C. Boreal Geothermal Inc. Page 26 02 JULY 2009...
Verify if 24VAC is present across Replace module if signal is pre- Stage 2 will not Y2 and C of the terminal strip. sent. Check wiring if signal is not activate present. 02 JULY 2009 Page 27 Boreal Geothermal Inc.
Page 28
Faulty compressor, not Pressures change only slightly from Replace compressor. pumping. static values when compressor is started. Boreal Geothermal Inc. Page 28 02 JULY 2009...
Page 29
Disconnect the water lines and Have a qualified service technician heat exchanger. check the inside of the pipes for backflush the coaxial exchanger. (typically for ground water, scale deposits. unlikely for ground loop) 02 JULY 2009 Page 29 Boreal Geothermal Inc.
Page 30
(does not occur pressor to run when it shouldn’t, tripping the low pressure control. while there) Intermittent Indoor circula- Verify wiring is good Correct the wiring or replace the tor. circulator. Boreal Geothermal Inc. Page 30 02 JULY 2009...
Page 31
15 psig or as high as 125 psi. The Voltmeter / controlling mechanism consists of a flexible Digital orifice that varies its area inversely with In-line Flowmeter pressure so that a constant flow is maintained. 02 JULY 2009 Page 31 Boreal Geothermal Inc.
The heat pump is now ready for repairs. Always ensure nitrogen is flowing through the system during any soldering procedures to prevent soot buildup inside the pipes. Boreal Geothermal Inc. recommends replac- ing the liquid line filter-drier anytime the refrigeration system has been exposed to the atmosphere.
Pumping unit bentonite grout. The grout is Bentonite grout seals the geothermal wells introduced into the geothermal wells from and ensured the best possible thermal the bottom and going up to the surface. conductivity. 02 JULY 2009 Page 47 Boreal Geothermal Inc.
Page 48
The geothermal heat pump is connected through a pumping module to ground loops that has previously been purged of air and filled with a suitable antifreeze. The unit is ready to operate Boreal Geothermal Inc. Page 48 02 JULY 2009...
Page 49
THIS PAGE INTENTIONALLY LEFT BLANK 02 JULY 2009 Page 49 Boreal Geothermal Inc.
Page 50
THIS PAGE INTENTIONALLY LEFT BLANK Boreal Geothermal Inc. Page 50 02 JULY 2009...
Page 51
THIS PAGE INTENTIONALLY LEFT BLANK 02 JULY 2009 Page 51 Boreal Geothermal Inc.
This warranty covers all internal components of the heat pump. BOREAL GEOTHERMAL INC. shall, at its option, repair or replace any part covered by this warranty. Defective parts shall be returned to BOREAL GEOTHERMAL INC., transportation charges prepaid.