AirStage ASYA004GTAH Installation Manual

AirStage ASYA004GTAH Installation Manual

Indoor unit (wall mounted type)
Hide thumbs Also See for ASYA004GTAH:

Advertisement

Quick Links

EEV internal model
ASYA004GTAH/ASHA004GTAH
ASYA007GTAH/ASHA007GTAH
ASYA009GTAH/ASHA009GTAH
EEV external model
ASYE004GTAH/ASHE004GTAH
ASYE007GTAH/ASHE007GTAH
ASYE009GTAH/ASHE009GTAH
ASYA030GTAH/ASHA030GTAH
ASYA034GTAH/ASHA034GTAH
TM

INSTALLATION MANUAL

INSTALLATIONSANLEITUNG
MANUEL D'INSTALLATION
UNITÉ INTÉRIEURE (Type montage mural)
MANUAL DE INSTALACIÓN
UNIDAD INTERIOR (Tipo montado en pared)
Únicamente para personal de servicio autorizado.
MANUALE DI INSTALLAZIONE
UNITÀ INTERNA (tipo montato a parete)
A uso esclusivo del personale tecnico autorizzato.
ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ
ΕΣΩΤΕΡΙΚΗ ΜΟΝΑΔΑ (Επιτοιχιος Τύπος)
Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό.
MANUAL DE INSTALAÇÃO
РУКОВОДСТВО ПО УСТАНОВКЕ
ВНУТРЕННИЙ МОДУЛЬ (настенного типа)
Только для авторизованного обслуживающего персонала.
INDOOR UNIT (Wall Mounted Type)
For authorized service personnel only.
INNENGERÄT (wandmontierter Typ)
Nur für autorisiertes Fachpersonal.
Pour le personnel agréé uniquement.
UNIDADE INTERIOR (Tipo mural)
Apenas para técnicos autorizados.
MONTAJ KILAVUZU
İÇ ÜNİTE (Duvara Monteli Tip)
Yalnızca yetkili servis personeli için.
Refer to the rating label with the serial number.
MADE IN THAILAND
[Original instructions]
PART No. 9373370345

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ASYA004GTAH and is the answer not in the manual?

Questions and answers

Summary of Contents for AirStage ASYA004GTAH

  • Page 1: Installation Manual

    INSTALLATION MANUAL INDOOR UNIT (Wall Mounted Type) For authorized service personnel only. INSTALLATIONSANLEITUNG EEV internal model INNENGERÄT (wandmontierter Typ) ASYA004GTAH/ASHA004GTAH Nur für autorisiertes Fachpersonal. ASYA007GTAH/ASHA007GTAH ASYA009GTAH/ASHA009GTAH MANUEL D’INSTALLATION UNITÉ INTÉRIEURE (Type montage mural) EEV external model ASYE004GTAH/ASHE004GTAH Pour le personnel agréé uniquement.
  • Page 2: Table Of Contents

    INSTALLATION MANUAL This mark indicates procedures which, if improperly performed, CAUTION PART No. 9373370345 might possibly result in personal harm to the user, or damage VRF system indoor unit (Wall mounted type) to property. Read carefully all security information before use or install the air conditioner. Contents Do not attempt to install the air conditioner or a part of the air conditioner by yourself.
  • Page 3: Accessories

    2.3. Accessories 3. INSTALLATION WORK Correct initial installation location is important because it is difficult to move unit after it is WARNING installed. For installation purposes, be sure to use the parts supplied by the manufacturer or other 3.1. Selecting an installation location prescribed parts.
  • Page 4: Installation Dimension

    004/007/009 model 3.2. Installation dimension Wall hook bracket 004/007/009 model 80 mm or Wall hook bracket more (*1) Right side Left side 200 mm or 70 mm or more (*2) more (*2) Tapping screw (accessory, 5 pcs) 030/034 model 1500 mm 1800 mm or Wall cap or more...
  • Page 5: Pipe Installation

    3.3.5 Forming the drain hose and pipe 004/007/009 model (3) Bend the connection piping at the bend radius of 70 mm or more and install no more CAUTION than 35 mm from the wall. Insert drain hose and drain cap securely. Drain should slope down to avoid water leak- 030/034 model age.
  • Page 6: Pipe Requirement

    4.3.3 Pipe connection 4.2. Pipe requirement When the flare nut is tightened properly by your hand, hold the body side coupling with a separate spanner, then tighten with a torque wrench. CAUTION CAUTION Refer to the installation manual for the outdoor unit for description of allowable pipe length and height difference.
  • Page 7: Electrical Requirement

    5.2. Wiring method CAUTION Earth (Ground) the unit. Example Do not connect the earth (ground) cable to a gas pipe, water pipe, lightning rod, or a Outdoor unit or RB unit *1 telephone earth (ground) cable. Improper earthing (grounding) may cause electric shock. Transmission Do not connect power supply cable to the transmission or remote controller terminals, as this will damage the product.
  • Page 8: Wiring

    B. For strand wiring 5.4. Wiring (1) Use ring terminals with insulating sleeves as shown in the figure below to connect to the terminal block. (1) Open the intake grille. Refer to “8. FRONT PANEL REMOVAL AND INSTALLATION”. (2) Securely clamp the ring terminals to the cables using an appropriate tool so that the (2) Remove the wire cover and remove the cable clamp.
  • Page 9: Field Setting

    • If working in an environment where the wireless remote controller can be used, the ad- 6. FIELD SETTING dresses can also be set using the remote controller. • If setting the addresses using the wireless remote controller, set the indoor unit address There are 3 methods for address setting by FIELD SETTING as follows.
  • Page 10: Function Setting

    ○ 6.3. Function setting 00 All Change the target for reporting er- Display only Error report rors. Errors can either be reported WARNING target on central in all locations, or only on the remote central remote controller. Please make this setting after completing all construction works. controller Follow the When set to 01, the fan stops when...
  • Page 11: External Input And External Output (Optional Parts)

    6.3.2 Checking the function settings 6.4. External input and external output (Optional parts) Press and hold the “MANUAL AUTO” button on the indoor unit for 3 seconds to check the function settings. It is necessary to disconnect the power in order to return to normal In this setting, you need to remove the front panel.
  • Page 12: External Output

    When connected to Apply voltage terminals of multiple indoor units with a connected unit, [In the case of “Pulse” input] be sure to make a branch outside the indoor unit using a pull box, etc. as shown on below Connector Input signal Command example.
  • Page 13: Finishing

    Operation behavior 7. FINISHING Connector Output voltage Status Stop CAUTION External output 1 Pins 1-2 DC 12 V Operation After checking for gas leaks (refer to the Installation Manual of the outdoor unit), perform this section. Normal External output 2 CNB01 Install heat insulation around both the large (gas) and small (liquid) pipes.
  • Page 14: Front Panel Removal And Installation

    8. FRONT PANEL REMOVAL AND INSTALLATION 8.3. Front panel installation 004/007/009 model 8.1. Intake grill removal and installation (1) Firstly, fit the lower part of the front panel, and insert top and bottom hooks. ( 3 top Intake grill removal Intake grill installation sides, 6 bottom sides) Open the intake...
  • Page 15: Error Codes

    Wired Remote Controller Display 11. ERROR CODES UTY-RNR*Z2 (2-wire type) If you use a wired type remote controller, error codes will appear on the remote controller display. If you use a wireless remote controller, the lamp on the photodetector unit will Touch the [Next Page] (or [previous page]) output error codes by way of blinking patterns.

Table of Contents