Page 1
Commercial Refrigerator Service Manual GLASS DOOR MERCHANDISER SMG12 Please read this manual completely before attempting to install or operate this equipment.
4. MAIN COMPONENTS 4-1. COMPRESSOR MODEL SMG12 Refrigerant R-134a Voltage 115V/60Hz Comp. NE2121Z Model Part code 27R.33 4-2. COMPRESSOR RELAY SMG12 Voltage 115V / 60Hz Relay HLC-1XT04XA Model 4-3. CONDENSER DRYER MODEL SMG12 Refrigerant R-134a Spec. XH-9 25g Part code GN1410TN.14...
4-6. CONDENSER FAN MOTOR MODEL SMG12 115V / 60Hz Voltage Motor CA27-04/C19 Model Part code 27F.11 4-7. EVAPORATOR DEFROST HEATER MODEL SMG12 Voltage 115V / 60Hz Spec. Part code 4-8. LAMP MODEL SMG12 115V/60Hz Voltage Spec. T8 28W Part code HGD-12R.21...
5. ELECTRONIC CONTROLLER INSTRUCTION 5-1-1. DIXELL XR20C PARAMETER FOR REFRIGERATOR NO.1 SMG12 ℃ ℉ Label Name Range Hidde Defau ℃ /℉ Par. Set point LS-US -5/23 Differential 0.1-25.5℃ /1- 2/35.6 255℉ -50℃ -SET/- Minimum set point -50/- 58℉ -SET Maximum set point...
Page 13
cycles (Maximum) length 0-255min defrost Display during defrost rt, it, Set, DEF MAX display delay after 0-255min defrost Defrost delay after fast 0-23h 50’ freezing Temperature Alarm rE=related to configuration set;Ab=absol MAX. temperature alarm SET- 110/23 110℃/SET- 230℉ MIN. temperature alarm -50℃-SET/- -50/- 58℉-SET...
Page 14
Evaporator probe display Software release Map code 5-1-2. 1. FRONT PANEL COMMANDS To display target set point, select a parameter or confirm an operation in programming mode. To start a manual defrost To view the last alarm occurrence. In programming mode, it browses the parameter codes or increases the display value To view the last alarm occurrence.
Page 15
2. MAIN FUNCTIONS 2.1 HOW TO VIEW THE SET POINT 1. Push and immediately release the SET key: the display will show the set point value. 2. Push and immediately release the SET key or wait for 5 seconds to display the sensor value again.
6. REPLACEMENT OF MAIN COMPONENTS 6-1. FRONT PANEL PARTS 6-1-1. UNSCREW THE FRONT PANEL. 6-1-2. TAKE OFF THE FRONT PANEL 6-1-3. UNSCREW THE JUNCTION BOX. THE MAIN SWITCH, LIGHT SWITCH AND THERMOSTAT CAN BE CHANGED.
6-2. REFRIGERATION COMPARTMENT PARTS 6-2-1. UNSCREW THE SENSOR CLIP .TAKE THE SENSOR OUT FROM THE CLIP. 6-2-2. Unscrew the circle fan cover. 6-2-3. PULL DOWN THE CIRCLE FAN COVER.
Page 18
6-2-4. UNSCREW THE FAN SUPPORT 6-2-5. CHANGE THE DEFROST HEATING ELEMENT. A. UNHOOK THE EVAPORATOR FROM ITS CASING.
B. TAKE OFF THE ELEMENT AND CHANGE IT. 6-3. CONDENSING UNIT 6-3-1. TAKE OFF THE BOTTOM PANEL.
Page 20
6-3-2. UNSCREW THE UNIT BOARD. YOU CAN PULL THE UNIT BOARD OUT FOR ANY REPAIR OR CLEANING. CAUTION: BE CAREFUL OF ELECTRIC SHOCK CAUTION: MAKE SURE THE POWER SUPPLY IS CUT OFF BEFORE ANY SERVICE IS PERFORMED. CAUTION: CONDENSING UNIT MAY BE VERY HOT. BE SURE IT IS COOL BEFORE ANY SERVICE IS PERFORMED.
Need help?
Do you have a question about the SMG12 and is the answer not in the manual?
Questions and answers