1. Version
Rev.
00
Issue spec.
01
Add sectioni 10
2. Description
2-1 . General
Delta Heat Exchanger (HEX) is designed for direct air to air heat
exchange to remove heat from the cabinet.
The internal and the external air circulation loops of the HEX are
separated to prevent the introduction of dust, humidity and dirt. The fan on
the external air loop conforms to IP55 protection rating.
2-2 . Specification
Outline Dimension (H x W x D)
Cooling Capacity (*Note 1)
Rated Voltage
Rated Current (*Note 2)
Operating Voltage Range
Operating Current
Operating Power Consumption
Acoustic Noise at 1.5M (SPL)
Weight
* Note1 : The cooling capacity (W/K , W/°C or W/℉) is defined as Q/ (TI-TA)
Q : Heat dissipation (W) from inside of cabinet
TI : Return temperature of internal air circuit (K , °C or ℉)
TA : Ambient temperature of external air circuit (K , °C or ℉)
*Note 2 : Rated current is announcement of safety
Description
Main feature
Page 1
HEX150PC Heat Exchanger Instruction Manual
Drawn
Approved
Nick Wang
Adam Chen
Nick Wang
Adam Chen
Unit
mm
(in)
W/K (W/℉)
100 (56)
VDC
A
VDC
A
W
dB-A
Kg (Lb)
Issue date
2016/1/25
2016/6/10
Model Number
HEX150PC
690 x 550 x 242
(27 x 22 x 10)
135 (75)
48
6.3
40 - 60
2.6
5.8
125
279
65.0
73.0
20 (44)