3 Prepare the installation of the fan coil unit
Information
The equipment described in this manual may cause electronic noise generated from
radio-frequency energy. The equipment complies to specifications that are designed
to provide reasonable protection against such interference. However, there is no
guarantee that interference will not occur in a particular installation.
It is therefore recommended to install the equipment and electric wires keeping
proper distances away from stereo equipment, personal computers, etc.
In extreme circumstances a distance of 3 m or more is required.
Electrical characteristics
Model
Phase
Frequency (Hz)
Voltage range (V)
Voltage tolerance (V)
Maximum running current (A)
Overcurrent fuse (A) (field supply)
Table 3.2: Electrical characteristics
(a)
In case of common power supply to more than one unit (as illustrated in figure
remote controllers" on page
Branch the line outside the terminal block of the unit in accordance with electrical equipment standards, when
using two power wires of a gauge greater than 2 mm². The branch must be sheathed in order to provide an equal
or greater degree of insulation as power supply wiring itself.
Specifications for field wiring
Power supply wiring
Remote controller
and unit transmission
wiring
Table 3.3: Field wiring specifications
(a)
Only in case of protected pipes. Use H07RN-F in case of no protection.
(b)
Run electrical wiring through a conduit to protect against external forces.
(c)
Use double insulation wire for remote controller (sheath thickness: ≥1 mm) or run wires through a wall or
conduit so that the user cannot come in contact with them.
(d)
This length is the total extended length in the system in case of group control. See figure
with 2 remote controllers" on page
Prepare the installation of optional equipment
Installation manual
8
FWF
1N~
50
220-240
±10%
0.9
(a)
16
19), keep total current of interconnection wiring between units less than 12 A.
Wire
According to the
(a),(b)
H05VV-U3G
legislation. Max. 4.0
Sheathed wire
(c)
2 conductors
19.
"Group control or use with 2
Size (mm²)
Length
applicable
0.75-1.25
Max. 500 m
"Group control or use
4PW64524-1 – 09.2010
(d)
FWF