Setup Simultaneous Control of Centralized Controller and the ERV Wired Remote Control
The centralized controller can be controlled by RMC ADDRESS of the ventilator, while the ERV wired remote
controller is controlled by COM2 communication.
Centralized Controller
Master Ventilator
Transmitter 0
ERV Wired
Remote Control
COM2 (F3, F4)
The ERV wired remote control is MASTER of COM2 communication, so it can communicate without
separate ADDRESS setting.
Level Setup of Centralized Controller
You can control the ventilator in multiple ways with DIP switch (DS01) setting on the centralized controller.
DIP Switch
SW01
SW02
LEVEL 0
OFF
OFF
LEVEL 1
ON
OFF
LEVEL 2
OFF
ON
LEVEL 3
ON
ON
MAIN:0
RMC:0
COM1 (F1, F2)
Ventilator
MAIN:1
RMC:0
SW03
SW04
OFF
OFF
The ventilator operates with the last used control solution
When the centralized controller is OFF:
You can not use wired/wireless remote control.
OFF
OFF
When the centralized controller is ON:
You can use wired/wireless remote control.
OFF
OFF
The ventilator operates only with the centralized controller.
If the On/Off button is pressed once :
The operation indicator is turned on. The ventilator is on standby.
The ventilator operated with wired/wireless remote control.
OFF
OFF
If the On/Off button is pressed twice:
The operation indicator is turned off.
You can not operate the ventilator with wired/wireless remote control.
Ventilator
Ventilator
MAIN:2
MAIN:3
RMC:0
RMC:0
Remark
Ventilator
MAIN:F
RMC:0