Table A-3 Electrical/Performance Specifications - Siemens SIMATIC 505 User Manual

Isolated interrupt discrete
Hide thumbs Also See for SIMATIC 505:
Table of Contents

Advertisement

Module
Rated Voltage DC
Input voltage range for ON
VDC UH minimum
VDC UH maximum
Input voltage range for OFF
VDC UL minimum
VDC UL maximum
Input current limits during ON
mA IH minimum
mA IH maximum
Input current for OFF
mA maximum
Number of inputs
Delay time through module
Module power from base
SIMATIC 505 Interrupt Input Module User Manual

Table A-3 Electrical/Performance Specifications

PPX:505–4317
24
10.0
30.0
–30.0
3.0
2.0
10.0
0.5
16 points in non-interrupt mode (16 Xs) 32 points
in interrupt mode (24 Xs, 8 Ys):
16 physical input points (16 Xs)
8 internal logic input points (8 Xs)
8 internal logic output points (8 Ys)
0.5 ms maximum, filter off
10 ms maximum, filter on
2.0 W maximum (1.6 W typical) at +5 V
PPX:505–4318
PPX:505–4319
48
125
43.0
112.5
53.0
137.5
–30.0
–30.0
10.0
25.0
1.0
1.0
6.0
4.0
0.5
0.5
Specifications
A-3

Advertisement

Table of Contents
loading