Daikin FVXG25K2V1B Service Manual page 121

Pair, floor standing type k-series, heat pump, indoor/outdoor units
Hide thumbs Also See for FVXG25K2V1B:
Table of Contents

Advertisement

SiBE061121
Troubleshooting
Check No.17
Refer to P.128
Check No.19
Refer to P.129
25/35 class
50 class
Service Diagnosis
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Turn off the power and turn it on
again.
Error again or outdoor
fan activated?
NO
Check No. 19
Check the outdoor fan or
related.
OK
Radiation fin dirty?
Slightly dirty
Check No. 17
Check the installation condition.
A (°C)
98
95
To cool the electrical components,
the outdoor fan starts when the
radiation fin temperature rises
above C ˚C and stops when it
drops below B ˚C.
YES
Check the radiation fin
temperature.
Above
A ˚C?
YES
NG
Too dirty
B (°C)
C (°C)
75
83
80
85
Troubleshooting
WARNING
NO
Replace the outdoor unit
PCB.
Replace the fan motor.
Correct the connectors
and fan motor lead wire.
Replace the outdoor unit
PCB.
Clean up the radiation fin.
(R14444)