2-2. For AU*30/ 36/ 45/ 54LUAS
The compressor frequency soon after the start-up is controlled as shown in Figure 10.
(Fig.10 : Compressor Control at Start-up)
Frequency
Hold
Frequency
Time A
(Frequency)
AU*30LUAS
AU*36LUAS
AU*45LUAS
AU*54LUAS
(Time)
AU*30LUAS
AU*36LUAS
AU*45LUAS
AU*54LUAS
1
2
Time B
Time C
Time E
Frequency
Frequency
40Hz
56Hz
56Hz
70Hz
Time A
Time B
180sec
60sec
180sec
80sec
05-10
For AU*30/ 36LUAS
1 Discharge pipe temp. >
2 Discharge pipe temp. < 30°C
For AU*45/ 54LUAS
1 Discharge pipe temp. >
2 Discharge pipe temp. < 35°C
Time C
Time D
120sec
120sec
180sec
180sec
Time D
30°C
=
35°C
=
Time E
720sec
720sec