Occupancy Sensor OCS 100W • Setup Guide
The OCS 100W is a wall-mounted occupancy sensor that incorporates ultrasonic (US) and passive infrared (PIR) into a dual-
technology sensor. The US sensor emits ultrasonic sound waves into an area and measures the speed of their return to detect
the presence of people. Frequency changes are caused by the movement of people, which is detected by the US waves. The PIR
sensor detects the presence of people based on the difference between the heat generated by moving people versus the ambient
room temperature.
The OCS 100W has a 24 VDC power input, ground/common connection, normally open/closed relay, photocell, and occupancy
output connections.
Front Panel Features
Ultrasonic
Sensors
Ultrasonic
Sensors
Figure 1.
OCS 100W Front Panel Features
Control
DIP Switches (A)
DIP Switches (A)
A
Timer Test Button
Red Dial
Green Dial
Timer Test Button
Red Dial
Figure 2.
OCS 100W Controls
•
DIP Switches (B) —
B
OPERATION
1
Timer Setting
(B1 and B2 switches
must be set together)
2
3
Timer adjust
4
Sensitivity adjust
*Default
•
Blue Timer Test Button —
Push in to enable 8 second timer mode. This will last for 1 hour. Then automatically resets to the dip switch settings.
•
Push and hold until the red LED flashes to return the 8 second timer to the dip switch timer settings.
•
Red Infrared Sensitivity Dial — Adjust this dial to increase or decrease infrared sensitivity.
•
Turn counter clockwise (CCW) to decrease sensitivity.
•
Turn clockwise (CW) to increase sensitivity.
•
Factory default is 75%.
•
Green LED
(status indicator)
Infrared Sensor and Lens
Green LED
(status indicator)
Red LED
Infrared Sensor and Lens
(status indicator)
Removable Front Cover
Red LED
(status indicator)
Removable Front Cover
DIP Switches (B)
DIP Switches (B)
B
A
B
Notch
Blue Dial
Notch
Blue Dial
Green Dial
OFF
8 minutes:
OFF*
OFF *
Automatic
Automatic
Ultrasonic Sensors — Detect movement in the room, based on
•
ultrasonic waves.
•
Green LED (status indicator) — Flashes when the ultrasonic
sensors detect occupancy.
Infrared Sensor and Lens — Diffracts the incoming light and
•
directs the light to the infrared sensor.
•
Red LED (status indicator) — Flashes when the infrared sensor
detects occupancy.
Removable Front Cover — Conceals all controls and DIP
•
switches.
•
DIP Switches (A) —
A
OPERATION
1
Not used
2
Not used
3
LED indicator
4
Automatic adjust
reset
*Default
ON
4 minutes:
15 minutes:
30 minutes:
OFF
ON
ON
ON
OFF
ON
Manual*
Manual*
OFF
ON
Not used*
Not used
Not used*
Not used
LED enabled*
LED disabled
Toggle to reset (Default: OFF)