Occupancy Sensor OCS 100W • Setup Guide
The OCS 100W is a wall-mounted occupancy sensor that incorporates ultrasonic (US) and passive infrared (PIR) into a dual-
technology sensor. The US sensor emits ultrasonic sound waves into an area and measures the speed of their return to detect
the presence of people. Frequency changes are caused by the movement of people, which is detected by the US waves. The PIR
sensor detects the presence of people based on the difference between the heat generated by moving people versus the ambient
room temperature.
The OCS 100W has a 24 VDC power input, ground/common connection, normally open/closed relay, photocell, and occupancy
output connections.

Front Panel Features

Ultrasonic
Sensors
Ultrasonic
Sensors
Figure 1.
OCS 100W Front Panel Features
Control
DIP Switches (A)
DIP Switches (A)
A
Timer Test Button
Red Dial
Green Dial
Timer Test Button
Red Dial
Figure 2.
OCS 100W Controls
DIP Switches (B) —
B
OPERATION
1
Timer Setting
(B1 and B2 switches
must be set together)
2
3
Timer adjust
4
Sensitivity adjust
*Default
Blue Timer Test Button —
Push in to enable 8 second timer mode. This will last for 1 hour. Then automatically resets to the dip switch settings.
Push and hold until the red LED flashes to return the 8 second timer to the dip switch timer settings.
Red Infrared Sensitivity Dial — Adjust this dial to increase or decrease infrared sensitivity.
Turn counter clockwise (CCW) to decrease sensitivity.
Turn clockwise (CW) to increase sensitivity.
Factory default is 75%.
Green LED
(status indicator)
Infrared Sensor and Lens
Green LED
(status indicator)
Red LED
Infrared Sensor and Lens
(status indicator)
Removable Front Cover
Red LED
(status indicator)
Removable Front Cover
DIP Switches (B)
DIP Switches (B)
B
A
B
Notch
Blue Dial
Notch
Blue Dial
Green Dial
OFF
8 minutes:
OFF*
OFF *
Automatic
Automatic
Ultrasonic Sensors — Detect movement in the room, based on
ultrasonic waves.
Green LED (status indicator) — Flashes when the ultrasonic
sensors detect occupancy.
Infrared Sensor and Lens — Diffracts the incoming light and
directs the light to the infrared sensor.
Red LED (status indicator) — Flashes when the infrared sensor
detects occupancy.
Removable Front Cover — Conceals all controls and DIP
switches.
DIP Switches (A) —
A
OPERATION
1
Not used
2
Not used
3
LED indicator
4
Automatic adjust
reset
*Default
ON
4 minutes:
15 minutes:
30 minutes:
OFF
ON
ON
ON
OFF
ON
Manual*
Manual*
OFF
ON
Not used*
Not used
Not used*
Not used
LED enabled*
LED disabled
Toggle to reset (Default: OFF)
1

Advertisement

loading

Summary of Contents for Extron electronics OCS 100W

  • Page 1: Front Panel Features

    Occupancy Sensor OCS 100W • Setup Guide The OCS 100W is a wall-mounted occupancy sensor that incorporates ultrasonic (US) and passive infrared (PIR) into a dual- technology sensor. The US sensor emits ultrasonic sound waves into an area and measures the speed of their return to detect the presence of people.
  • Page 2: Sensor Coverage

    Occupancy Sensor OCS 100W • Setup Guide (Continued) • Green Ultrasonic Range Dial (see figure 2 on the previous page) — Adjust this dial to increase or decrease ultrasonic sensitivity. Turn counter clockwise (CCW) to decrease sensitivity. • Turn clockwise (CW) to increase sensitivity.
  • Page 3: Installation

    20' - 0" Minor Motion Coverage 40' - 0" Major Coverage Sensory Coverage US Minor Motion IR Minor Motion OCS 100W Parts US Major Motion IR Major Motion Mounting Bracket Mounting Bracket Pull Wiring Pull Harness Wiring Harness Bracket Cover...
  • Page 4 Occupancy Sensor OCS 100W • Setup Guide (Continued) OCS 100W Wiring IPCP PRO 550 100-240V ~ 50-60Hz PWR OUT = 9W T x Rx G Tx R x G T x Rx G T x Rx G RTSCTS S G S G...
  • Page 5: Troubleshooting

    Troubleshooting Problem Possible Cause Test Result Sensor remains on. Constant noise. Reduce both green and red Move sensor to a less noisy knobs by 15% and remove area within the room. noise source. Sensor remains on too long. Timer setting too high. Check dip switch settings.
  • Page 6 Extron USA - West Extron USA - East +1.714.491.1500 +1.919.850.1000 +31.33.453.4040 +91.80.3055.3777 +1.714.491.1517 FAX +1.919.850.1001 FAX +31.33.453.4050 FAX +91.80.3055.3737 FAX 68-3155-50 Rev. B © www.extron.com 2017 Extron Electronics All rights reserved. All trademarks mentioned are the property of their respective owners. 09 17...