4.3. LCD Contrast

The factory setting is for optimum visibility at room temperature and in average light
conditions. Extremes of temperature will lessen the contrast.
Values
Adjust the value to improve visibility in different temperatures and luminosity. Change
the LCD contrast in small steps to ensure you can continue to read the display and to
prevent viewing difficulties.

4.4. PROFIBUS Ident Number (PROFIBUS IDENT)

Identifies the device on the network. The Ident Number must match that in the GSD
file (the GSD file provides information on the device to the master).
Options

4.5. Powered Hours

View only. Number of hours the unit has been powered up since manufacture.
To view via SIMATIC PDM, open the menu View – Wear.

4.6. Power-on Resets

View only. The number of power cycles that have occurred since manufacture.
To view via SIMATIC PDM, open the menu View – Wear.

4.17. Service Interval

Allows for scheduling of service inspections.
To access these parameters via SIMATIC PDM, open the menu Device –
Maintenance and click on the Service Schedule tab.
4.17.1. Time Last Serviced (TIME LAST SERV)
View only. Time elapsed since device was last serviced.
Can be reset to zero via the handheld programmer (after performing a service).
4.17.2. Remaining Lifetime (REMAIN LIFETIME)
View only. The sum of Total Service Interval less Time Last Serviced.
4.17.3. Maintenance Required Limit (MAINT REQ LIMIT)
If Remaining Lifetime is equal to or less than this limit, a Maintenance Required
status is generated.
Values
A5E32337685
SITRANS LR260 (PROFIBUS PA) – OPERATING INSTRUCTIONS
Range: 0 (High contrast) to 20 (Low contrast).
Default: Matches factory calibration for best visual contrast.
STD PROFILE
*
MANUFACTURER
STD – AIFB 1
ONL.
Range: 0 to 20 years
Default: 0. 1 64 years
Standard Profile (uses generic GSD for 2 AIFB
[ident # = 0x9701]
Manufacturer-specific (uses Siemens EDD and GSD
file, which identifies the LR260 [PROFIBUS PA])
[ident # = 0x8162]
Standard Profile AIFB 1 only (uses generic GSD for 1
AIFB) [ident # = 0x9700]