Installation Guide
Infl. - max. (room temp. limitation, max.) — A367.1
Circuit
2
Determines how much the desired flow temperature will be influenced
(decreased) if the actual room temperature is higher than the desired room
temperature (P control).
-9.9:
The room temperature has a big influence.
0.0:
The room temperature has no influence.
Infl. - max. (room temp. limitation, max.) — A367.2
Circuit
2
Determines how much the desired flow temperature will be influenced
(decreased) if the actual room temperature is higher than the desired room
temperature (P control).
-9.9:
The room temperature has a big influence.
0.0:
The room temperature has no influence.
Infl. - min. (room temp. limitation, min.)
Circuit
2
Determines how much the desired flow temperature will be influenced
(increased) if the actual room temperature is lower than the desired room
temperature (P control).
0.0:
The room temperature has no influence.
9.9:
The room temperature has a big influence.
88
DEN-SMT/DK
ECL Comfort 310, application A367
12182
Setting range
Factory setting
-9.9 ... 0.0
-4.0
12182
Setting range
Factory setting
-9.9 ... 0.0
0.0
12183
Setting range
Factory setting
0.0 .... 9.9
0.0