MEcHaNIcaL INStaLLatIoN
The charger can be wall or floor mounted. If wall mounted
make sure that the surface is free of vibrations and the char-
ger is mounted in a vertical position; if floor mounted make
sure that the surfaces are free of vibration, water, humidity.
You must avoid areas where the chargers may be splashed
with water.
The charger must be held by 2 or 4 fixings suitable for the type
of support. The drilling pattern varies according to the model
of charger (please refer to the technical data sheet).
ELEctrIcaL coNNEctIoN
To the mains supply
You may only connect to the 1-phase 230Vac or 3-phase
400Vac mains supply (depending on the type of the charger)
by means of a standard socket and an appropriate circuit
breaker (not supplied). The current consumption is shown on
the charger's information plate.
To the battery
Polarity must be observed. Any reversal of polarity will blow
the output fuse, prevent charging and cause DF2 fault code to
be displayed. Please refer to the Fault messages codes.
Connection to battery
The charger must be connected to the battery by the cables
supplied:
The RED cable: to the battery's POSITIVE terminal.
The BLACK cable: to the battery's NEGATIVE terminal.
5
6
7
6
Initiating charging
1. Connect the battery. If Default setting (autostart ON) then
the charge will start automatically else press the Start/
Stop button.
The display will show 3 different screens alternating
Screen 1:
Line 1
Line 2
Screen 2:
Line 1
Line 2
4
Screen 3:
Line 1
Line 2
Completion of charging
1. The LCD screen will give you the message of availability
(AVAIL)
The battery is charged and ready to use.
2. STOP the charge and disconnect the battery.
To stop the charge press the Stop/Start button.
Never disconnect the battery during charge without stopping
the charging process.
This could lead to dangerous sparks or to charger damage.
3. Completion of charging with equalization
Manual equalization only concerns vented lead/acid batteries.
It will be initiated manually or automatically by switch. All
other technologies will have an automatic preset equalization
time.
To force manual equalization keep pressed the equalization
button (right button) and contemporary click the On/Off (only
charging profiles for flooded). If automatic then the screen will
also show the following message:
Equalization mode auto
Days of the week (the symbol below indicates when the
equailzation is programed (e.g. Saturday and Sunday)
During equalization
Line 1. mode equal
Current / total voltage / remaining time
Charge mode / charging profile /
equal symbol (if selected) or no blocking fault
Charging current / total voltage / Ah+
Charge mode / charging profile /
equal symbol (if selected) or no blocking fault
Charging current / voltage/cell / charging time
Charge mode / charging profile /
equal symbol (if selected) or no blocking fault
Charging current / % state of charge /
estimated remaining time