Fujitsu AUG12LVLB Service Instruction page 42

Floor ceiling/slim duct/cassette type, inverter
Hide thumbs Also See for AUG12LVLB:
Table of Contents

Advertisement

Trouble shooting 7
INDOOR UNIT Error Method:
Indoor room thermistor error
Detective Actuators:
Indoor unit Controller PCB
Room temperature thermistor
Forecast of Cause :
1. Connector failure connection 2. Thermistor failure 3. Controller PCB failure
Check Point 1 : Check connection of Connector
Check if connector is loose or removed
Check erroneous connection
Check if thermistor cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
OK
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Rough value)
Temperature (°C)
Resistance Value (
Temperature (°C)
Resistance Value (
If Thermistor is either open or shorted, replace it and reset the power.
OK
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of each indoor unit and check terminal voltage at Thermistor (DC5.0V)
AU*G12/ 14/ 18LVLB
AR*G12/ 14/ 18LLTB
GRAY
1
1
CN5
GRAY
2
2
1
CN7
2
BLACK
1 1
CN8
BLACK
2 2
If the voltage does not appear, replace Controller PCB.
AMP Air Conditioning
Indicate or Display:
Refer to error code table.
Detective details:
Room temperature thermistor is open or short is detected always.
-10
-5
0
)
58.2
44.0
33.6
30
35
40
)
8.0
6.5
5.3
H/E (MID) Thermistor
Room Temp. Thermistor
5
10
15
25.9
20.2
15.8
45
4.3
AB*G18LVTB
BLACK
GRAY
1
1
1
1
CN5
BLACK
GRAY
2
2
2
2
1
CN7
2
Room Temp. Thermistor
BLACK
1 1
CN8
BLACK
2 2
www.ampair.co.uk | sales@ampair.co.uk
02-09
20
25
12.5
10.0
H/E (MID) Thermistor
DC