Outdoor Terminations - Vertical Venting; Vent Freezing Protection - Nordyne M4RC54D-24B Installation Instructions Manual

Single stage condensing gas furnaces m4rc series; m4rl series
Table of Contents

Advertisement

Vent Configuration to
Provide 12" Minimum
height above
Snow Level.
Outside
Wall
Figure 9. Alternate Horizontal Vent Installation
• Couplings are applied to the vent pipe on the interior
and exterior sides of the wall. NOTE: This insures the
pipe can not be pushed or pulled through the wall.
• The combustion air inlet pipe must have a 90 degree
termination elbow, and pointed downwards as shown
in
Figure 7 (page
11).

Outdoor Terminations - Vertical Venting

Termination spacing requirements from the roof and from
each other are shown in
• The roof penetration must be properly flashed and
waterproofed with a plumbing roof boot or equivalent
flashing.
• The combustion air intake must be provided with an
elbow opening downward.
Vent and combustion air piping may be installed in an
existing chimney which is not in use provided that:
• Both the exhaust vent and air intake run the length of
the chimney.
• The top of the chimney is sealed and weatherproofed.
• The termination clearances shown in
maintained.
• No other gas fired or fuel-burning equipment is vented
through the chimney.
Figure 10
Elbows on the combustion air
inlet must be positioned pointing
away from the exhaust vent.
12" Above Maximum
Expected Snow Level
(Both pipes)
Figure 10. Vertical Vent Termination
12
Figure 9
12" Min.
19" Max.
Support
12" Above
Maximum
Expected
Snow Level
1/2"
Armaflex
Insulation or
Equivalent
(if required)
Figure
10.
Figure 10
Plumbing Vent Roof Boot
(Both Pipes)

Vent Freezing Protection

When the vent pipe is exposed to temperatures
below freezing (i.e., when it passes through
unheated spaces, chimneys, etc.) the pipe
must be insulated with 1/2 inch thick sponge
rubber insulation, Armaflex-type insulation or
equivalent.Insulating pipe is important to avoid
condensate icing.
• When the vent pipe is exposed to temperatures below
freezing (i.e., when it passes through unheated spaces,
chimneys, etc.) the pipe must be insulated with 1/2
inch thick sponge rubber insulation, Armaflex-type
insulation or equivalent. Insulating pipe is important to
avoid condensate icing.
Table 2
lists the maximum length of flue pipe that can
travel through an unconditioned space or an exterior
space. The total vent length must not exceed the lengths
noted in
Table 1 (page
please refer to the Canadian Installation Code (CAN/
CGA-B149.1 or 2) and/or local codes.
• For extremely cold climates or conditions of short furnace
cycles (i.e. set back thermostat conditions), the last 18
inches of vent pipe can be reduced from 3" to 2-1/2",
3" to 2" or 2" to 1-1/1" if the total vent length is at least
15 feet in length and the vent is sized in accordance
with
Table
1. The length of the 2 inch pipe must not
be longer than 18 inches. Smaller vent pipes are less
susceptible to freezing, but must not be excessively
restrictive.
• To prevent debris or creatures from entering the
combustion system, a protective screen may be installed
over the combustion air intake opening. The screens
are
hole size must be large enough to prevent air restriction
Winter
Design
Temperature
Without Insulation
20
0
-20
* = Insulation thickness greater than 3/8 inch, based on an
R value of 3.5 (ft x F x hr) / (BTU x in.)
Table 2. Vent Protection
CAUTION:
10). For Canadian installations
Table 2
Maximum Flue Pipe Length
in Unconditioned and
Exterior Spaces
With Insulation
(feet)
(feet)*
45
20
10
70
70
60

Advertisement

Table of Contents
loading

This manual is also suitable for:

M4rc072d-35cM4rc108d-45dM4rl090-35cM4rc090d-35c

Table of Contents