Fujitsu AUXG45LRLB Service Instruction page 58

Cassette type inverter
Hide thumbs Also See for AUXG45LRLB:
Table of Contents

Advertisement

Trouble shooting 18
OUTDOOR UNIT Error Method:
Active filter voltage error
Detective Actuators:
Outdoor unit Main PCB
Active filter module
Transistor PCB
Forecast of Cause :
1. External cause
5. Transistor PCB failure
Check Point 1 : Check external cause at Indoor and Outdoor (Voltage drop or Noise)
Instant drop : Check if there is a large load electric apparatus in the same circuit.
Momentary power failure : Check if there is a defective contact or leak current
Noise : Check if there is any equipment causing harmonic wave near electric line.
(Neon bulb or electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
OK
OK
Check Point 2 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OK
OK
Check Point 3 : Check Active filter module
Check Active filter module.
>>If Active filter module is abnormal, replace it.
OK
OK
Check Point 4 : Check Transistor PCB
Check Transistor PCB
>>If Transistor PCB is abnormal, replace it.
OK
Check Point 5 : Replace Main PCB
If Check Point 1 - 4 do not improve the symptom, change Main PCB.
Indicate or Display:
Error code : 64
Detective details:
2. Connector connection failure
in the power supply circuit.
When inverter input DC voltage is higher than 430V or
lower than 110V.
When a momentary power cut off occurred on low voltage
3. Main PCB failure 4. Active filter module failure
02-20
Outdoor unit : No indication