7. FAN CONTROL FOR ENERGY SAVING
When the air flow setting except AUTO mode, the indoor fan motor will run as shown in Fig.8.
( Fig 8 : Indoor Fan Control)
ON
Compressor
OFF
Indoor fan
Setting air flow
480rpm
S-Lo
OFF
Setting Description
Disable
Enable
Remote controller
00 : When the outdoor unit is stopped, the indoor unit fan operates continuously following
the setting on the remote controller.
01 : When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very
low speed.
02 : Enable or disable this function by remote controller setting.
Set to "00"or "01"when connecting a remote controller that cannot set
the Fan control for energy saving function or connecting a network converter.
To confirm if the remote controller has this setting,
refer to the operating manual of each remote controller.
8. DEFROST OPERATION
When the defrost operation starts, the indoor fan runs according to cool air prevention control for 20 seconds.
And the fan is stopped if 20 seconds have passed.
When 60 seconds have passed after defrost operation is released,
the fan runs according to cool air prevention control.
10
30
(
Function Number
49
01-08
60
180
60
180
Factory setting)
Setting Value
00
01
02
(sec)
60
10
30