Maintenance; Error Code - Gree GWH24ACD-K3NNA1A Service Manual

Table of Contents

Advertisement

9. Maintenance

9.1 Error code

Display Method
No.
Malfunction
of Indoor Unit
Name
(Error Code)
Indoor ambient
temperature
1
sensor is
open/short-
circuited
Indoor
evaporator
temperature
2
sensor is
open/short-
circuited
Blocked
3
protection of
IDU fan motor
Malfunction
4
protection of
jumper cap
Overload
5
malfunction
Zero-crossing
inspection
circuit
6
malfunction
of the IDU fan
motor
30
A/C Status
The unit will stop operation as it
reaches the temperature point.
During cooling and drying operation,
F1
except IDU fan motor operates, other
loads stop operation; During heating
operation, the system stops operation.
The unit will stop operation as it
reaches the temperature point.
During cooling and drying operation,
F2
except IDU fan operates, other
loads stop operation; During heating
operation, the complete unit stops
operation.
IDU fan, ODU fan, compressor and
electric heat tube stop operation.
H6
Horizontal louver stops at the current
position.
Operation of remote controller or
C5
control panel is available, but the unit
won't act.
E8
The entire unit stops.
Operation of remote controller or
U8
control panel is available, but the unit
won't act.
Possible Causes(For specific maintenance
method, please refer to the following procedure of
troubleshooting)
1.The wiring terminal between indoor ambient temperature
sensor and main board is loosened or poorly contacted;
2.There's short circuit due to trip-over of the parts on
controller;
3.Indoor ambient temperature sensor is damaged (Please
check it by referring to the resistance table for temperature
sensor)
4. Main board is broken.
1.The wiring terminal between indoor evaporator
temperature sensor and main board is loosened or poorly
contacted;
2.There's short circuit due to the trip-over of the parts on
controller;
3.Indoor evaporator temperature sensor is damaged
(Please check it by referring to the resistance table for
temperature sensor)
4. Main board is broken.
1.The feedback terminal of PG motor is not connected
tightly.
2.The control terminal of PG motor is not connected tightly.
3.Fan blade rotates unsmoothly.
4.Malfunction of motor
5.Main board is broken.
1.There's not jumper cap on the main board.
2.Jumper cap is not inserted properly and tightly.
3.Jumper cap is damaged.
4.Controller is damaged.
1.Indoor and outdoor heat exchanger is too dirty?
Or air inlet/outlet is blocked?
2.Fan motor is not working. Abnormal fan speed; fan
speed is too low or the fan doesn't run.
3.Compressor operates normally or not? Is there any
abnormal noise or oil leak? Casing is too hot?
4.System is blocked inside? (Dirt blockage? Ice blockage?
Oil blockage? Y-valve is not fully open?)
5.Main board temperature sensor detects wrongly.
1.Quick de-energization and energization. Wrong
judgement by the controller because the electric-
discharging of capacitor is slow.
2.Zero-crossing inspection circuit of main board for
controller is abnormal.
Service Manual
Installation and Maintenance