MODELS CSW24V AND CSW24VH
MANUAL DISCONNECT
Press the reset switch to RESET/DISCONNECT. Release the handle on the operator arm
to allow the gate to be opened and closed manually. On a dual gate application the
handle must be released on both operators. To resume normal function tighten the
handle by pushing it down.
RESET SWITCH
The reset switch is located on the front of the operator and serves several functions.
Toggling the reset switch will stop a moving gate during a normal open/close cycle,
like a stop button. The operator does not need to be reset after doing this. The reset
switch will disable the gate in the present position and will energize the solenoid lock
for two minutes and disable the maglock for two minutes.
LOOP DETECTOR
WIRING
EXPANSION BOARD
Shadow Loop
Exit Loop
Interrupt Loop
OPERATION
BLUE LED
WHITE LED
1 Blink (every 10
OFF
seconds)
2 Blinks
Rapid Blinks (active fault)
or OFF
3 Blinks
Rapid Blinks (active fault)
or OFF
4 Blinks
Rapid Blinks (active fault)
OFF
2 Blinks
OFF
Slow Blinks
Solid
Solid
DIAL SETTINGS
TEST Mode
1-8
Determines the sensitivity setting for the loop detector:
1 is the lowest sensitivity (large vehicle) setting and 8 is the
highest sensitivity (small vehicle). Default setting is 4.
PROG Mode
White LEDs
(located under dial)
Frequency Button
Blue LED
(located under dial)
EXPLANATION
Normal Operation
Open Loop (see TROUBLESHOOTING)
Shorted Loop (see TROUBLESHOOTING)
Failed Authentication (see
TROUBLESHOOTING)
Successful Reset
Loop detector is in TEST or PROG mode
Active Loop
EXPLANATION
Used to test the loop detector
Used to change the frequency of the loop detector
Boost Switch
Dial
Manual Disconnect
Handle
TROUBLESHOOTING
Open or Shorted Loop (2 and 3 Blink errors):
Test the loop detector (refer to TEST THE LOOP DETECTOR section). If the loop
detector passes the test, this indicates the loop detector is working properly and there
is an issue with the loop wiring.
Failed Authentication (4 Blink error):
• Check the wire connecting the expansion board to the main board or
• Unplug the loop detector then plug it back into the same slot (clears all faults and
keeps the current frequency settings, authenticates) or
• Unplug the loop detector. Then unplug the J15 plug on the operator's control
board and plug it back in after 2-3 seconds. This allows the loop detector to be
plugged into a different slot (clears all faults and keeps the current frequency
settings, authenticates).
To clear a fault:
• Press the reset button on the operator (clears all faults) or
• Unplug the loop detector then plug it back into the same slot.
The loop is making false detections:
• There is crosstalk between the LOOPDETLM and the alternate loop detector or
• Change the frequency or lower the sensitivity setting of the loop detector.
The loop will not activate when a vehicle passes over it:
• Turn the boost switch ON or increase the sensitivity of the loop detector or
• If the blue and white LEDs are solid, indicating an Active Loop, and the operator
does not activate, there could be a fault. Once the loop is inactive, check the LED
codes for a fault (refer to LED table above).
TEST THE LOOP DETECTOR
1
Turn the dial to TEST. The loop detector will send a signal to the main board
simulating a vehicle over the loop.
Exit: If the gate is closed, it will open or if the gate is already open it will
remain open.
Shadow: Active ONLY when the gate is in the open position. If the gate is
open, it will remain open.
Interrupt: If the gate is closing, it will open.
2
Turn the dial back to the desired sensitivity setting.
2
NORMAL OPERATION
RESET/DISCONNECT