Start-up
Operation
1. Check
junction
moisture. Moisture may cause
chattering of relays/contactors.
2. WARNING! Live voltage
can kill! Check incoming
power volt age to make sure
that it is correct for panel
and mixer model.
3. Energize control panel. (Turn
on power to panel.)
4. WARNING! Live voltage
can kill! Check voltage to the
panel and at secondary of
control trans form er using a
voltmeter. If no transformer
is supplied, check volt age at
the circuit breakers.
5. Set the application specific
parameters for the VFD.
a. With power to the VFD
and the H-O-A switch in
the Off position, power
Mixer Model
HBM200M6-4/HBMX200DC
HBM200M3-4/HBMX200EC
HBM200M4-4/HBMX200FC
HBM200M6-6/HMBX200DB
HBM200M3-6/HBMX200EB
HBM200M4-6/HBMX200FB
Speed charts – FOR REFERENCE ONLY.
4
on hit the Menu button
until the pointer is above
main menu.
b. Use up and down key to
box
for
switch parameter groups.
Hit OK to set a parameter
group.
c. Use up and down key to
switch parameters. Hit OK
to set a parameter group.
Use up and down key to
change parameters. After
each change hit OK again
to set the value.
d. Use the back button to
get back to the parameter
groups.
e. Parameters to be set at
installation:
i. Set 1-24 motor current;
ii. Set 1-25 motor nominal
Amps
8
7
3.5
5.5
4.8
2.4
see chart below.
speed; 1150 or 1750;
see chart below.
Speed
Voltage
1750
200
1750
230
1750
460
1150
200
1150
230
1150
460
iii. Set 1-29 AMT; set to 2
and follow instructions
then set back to 0.
iv. Set 3-02 speed in Hz;
30–60 Hz.
f. Hit auto on button and
move H-O-A switch to
Auto position. When timer
contact is closed motor
should run.
WARNING: Do not exceed
60 Hz or go below 30 Hz.
Exceeding 60 Hz will draw
more horsepower from the
motor than it was designed for.
Running at lower than 30 Hz
may not supply enough starting
torque to the mixer unit.
6. With H-O-A switch in Hand,
check mixer to ver i fy the
mixer is run ning. On three
phase power, check to see if
each mixer has prop er ro tation.
7. Check full load current with
amp probe and compare it
with the name plate rat ing.
On three phase mixers, check
all three phases. Use a true
RMS meter to obtain accurate
readings.
8. Set range and adjustment
settings on timer.
a. Select one of the 16 built-in
time ranges by setting the
rotary switch per a chart on