• When cooling operation does not work.
1. Disconnect the lead wire leading to the compressor.
2. 3 minutes after turning ON the power supply, start EMERGENCY
OPERATION in COOL mode.
Is there voltage of 230 V AC between pin1
and pin2 at connector CN712?
Yes
Turn OFF the power supply.
Disconnect the connector CNAC2.
Is there normal resistance
to R.V. coil? (Refer to 11-5.)
Yes
Replace the 4-way valve.
• When heating operation does not work.
1. Disconnect the lead wire leading to the compressor.
2. 3 minutes after turning ON the power supply, start EMERGENCY
OPERATION in HEAT mode.
Is there voltage of 230 V AC between pin1
and pin2 at connector CN712?
Yes
Replace the outdoor control P.C. board.
OBH626L
No
No
Replace the R.V. coil.
No
Is there voltage 230 V AC
between the pin1 and pin3 at
connector CNAC?
Yes
Replace the outdoor
control P.C. board.
Replace the 4-way valve.
154
CNAC
Outdoor control
CN712
P.C. board
Outdoor power
CNAC2
P.C. board
No
Replace the outdoor
power P.C. board.