Mitsubishi MXZ-2D33VA Service Manual page 141

Outdoor unit
Hide thumbs Also See for MXZ-2D33VA:
Table of Contents

Advertisement

11-6. TROUBLESHOOTING FLOW
• When outdoor unit does not operate, LED on outdoor P.C. board is not lighting.
Check of power supply
MXZ-2D33VA/2D40VA/2D42VA/2D42VA2/2D53VA/2D53VA2
MXZ-2D53VAH/2D53VAH2
Check the main power supply circuit for proper connections.
Turn ON the power supply.
Is there voltage of 230 V AC in the
power supply terminal block?
Yes
Is there voltage of 230 V AC between
LD66B and X64
P.C. board?
Yes
Is there voltage of 230 V AC between
LD66A and LD70 on the inverter
P.C. board?
Yes
Is there voltage of 325 V DC between
DB61
+
and DB61
P.C. board?
Yes
Is there voltage of 5 V DC between
CN936
and CN936
outdoor display P.C. board?
Yes
Replace the outdoor display P.C. board.
OBH626L
No
No
on the inverter
No
No
-
on the inverter
No
on the
Check the power supply and correct them.
Replace the inverter P.C. board.
Replace the reactor.
Replace the inverter P.C. board.
Check the connected wire between
the inverter P.C. board and outdoor
display P.C. board and correct it.
Replace the inverter P.C. board.
141