Lennox FCA 60 Installation, Operation And Maintenance Manual page 72

Rooftop flexy
Table of Contents

Advertisement

USING THE KP02 MAINTENANCE CONTROL DISPLAY
V 068
[Statute] Gas grade
0 =
not configured
6 =
activation of a defect
V 069
[Statute] Humidifier
0 =
not configured
6 =
activation of a defect
V 070
[Regulation] Real set point, Cooling, Room
V 071
[Regulation] Real set point, Heating, Room
V 072
[Regulation] Power-factor, Cooling, Room
V 073
[Regulation] Power-factor, Heating, Room
V 074
[Regulation] Real set point, Supply
V 075
[Regulation] Power-factor, Cooling, Supply
V 076
[Regulation] Power-factor, Heating, Supply
V 077
[Regulation] Real set point, Dehumidification, Room
V 078
[Regulation] Real set point, Humidification, Room
V 079
[Regulation] Power-factor, Dehumidification, Room
V 080
[Regulation] Power-factor, Humidification, Room
V 081
[Mode] Number of the active mode
V 082
[Function] Number of the unit in standby
V 083
[Defects] Memory, Code
V 084
[Defects] Memory, Hour
V 085
[Defects] Memory, Minute
V 086
[Defects] Memory, Day
V 087
[Defects] Memory, Month
V 088
[Information] Non-standard program
V 089
[Information] Number of version of the program
CONFIGURATION
This information is taken into account by the program after having switched off/on the CLIMATIC, and a second time for C091
and C093 setpoints.
Set point 'Eeprom'
(KP02 C.083)
Maximum percentage of power of electrical heater
(KP02 C.090)
On = KP17 in ON/OFF mode
(KP02 C.091)
J.Bus - Number of slave (KP06, KP07, CLIMALINK, CLIMALOOK)
(KP02 C.093)
Link - Identification number
(KP02 C.094)
Link - Number of connected cards
(KP02 C.095)
Link - Functions
(KP02 C.096)
Link - Room Temperature and Humidity
(KP02 C.097)
Link - Outside Temperature and Humidity
(KP02 C.098)
See tables below
(KP02 C.100)
On = Option Bi-Speed of the blower
(KP02 C.101)
On = Option Regulation all seasons
(KP02 C.102)
On = Option optimised defrost
(KP02 C.103)
On = Option Enthalpy and management of the humidity
Page 70 - IOM / ROOF-TOP FLEXY™ Series
1, 2 or 3 = number of stages
8 =
ventilation no ready
1 =
ok
8 =
ventilation no ready
1
1
2
2
1
1
1
1
1
1
1
1
1